INSP-Final Inspection | 2/5/2020 | 2/6/2020 | 2/6/2020 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. Previous corrections have been addressed.
Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|
INSP-Final Inspection | 2/4/2020 | 2/5/2020 | 2/5/2020 | A | FAIL |
Troy Cobbley
|
|
|
Left message I was on the way. Arrived tried calling again but made no contact. No inspection perfromed.
Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|
INSP-Final Inspection | 1/29/2020 | 1/30/2020 | 1/30/2020 | A | FAIL |
Jim Page
|
|
|
Dry sidewall in addition needs to comply with table 8.4.9.1 or provide an observed ambient temperature of vehicle bay to show what temperature the barrel length will be exposed too.
Contact: Steve Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|
Plan assigned to (Stumbaugh) | 1/28/2020 | | 1/29/2020 | | DONE |
Mark Stumbaugh
|
|
|
Plan mod
|
Sprinkler Plan Check | 1/29/2020 | | 1/29/2020 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/29/2020 | | DONE |
Mark Stumbaugh
|
|
|
As Builts
No Review required
|
Permit Ready to Issue | | | 1/29/2020 | | DONE |
|
|
|
as built met
|
CHANGE STATUS TO (ISS) | | | 1/29/2020 | | DONE |
|
|
|
|
Plan Modification Accepted | | | 1/28/2020 | | DONE |
|
|
|
plan mod workflow started per email request by Hunter Fillmore. Changed the model of dry sprinkler head in the space from 8.1K factor to 5.6K factor, the coverage is unchanged.
|
Issue and Print Permit | | | 1/22/2020 | | DONE |
|
|
|
|
Intake Approval | | | 1/21/2020 | | PASS |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 1/21/2020 | | 1/21/2020 | | DONE |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 1/21/2020 | | 1/21/2020 | | PASS |
Mark Stumbaugh
|
|
|
|
1st review completed | | | 1/21/2020 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/21/2020 | | DONE |
Mark Stumbaugh
|
|
|
|
Permit Ready to Issue | | | 1/21/2020 | | DONE |
|
|
|
met
|
Application received | | | 1/20/2020 | | DONE |
|
|
|
Application submitted via PDS Online on Jan 20 2020 4:58PM
|