INSP-Final Inspection | 2/11/2020 | 2/12/2020 | 2/12/2020 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
Plan assigned to (Lee) | 2/7/2020 | | 2/10/2020 | | DONE |
Lee G Meredith
|
|
|
plan mod
|
1st review completed | | | 2/10/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 2/10/2020 | | 2/10/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 2/10/2020 | | DONE |
|
|
|
Quick permit plan mod passed
Fees include 2 hours of review / coordination time at $65 per hour and 3 hours of inspection time at $55 per hour for temporarily installed 6820 fire alarm panel. $130 + $165 = $295 total permit fee.
|
Permit Ready to Issue | | | 2/10/2020 | | DONE |
|
|
|
plan mod passed
|
Issue and Print Permit | | | 2/10/2020 | | DONE |
|
|
|
|
Plan Modification Accepted | | | 2/7/2020 | | DONE |
|
|
|
Dante from Apex requested a plan mod workflow
|
INSP-Final Inspection | 2/6/2020 | 2/7/2020 | 2/6/2020 | A | CANC |
Troy Cobbley
|
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Thursday, February 06, 2020.
|
INSP-Final Inspection | 2/5/2020 | 2/6/2020 | 2/6/2020 | A | FAIL |
Greg Ruxton
|
|
|
Permit failed based on noted deficiencies: induct smoke detector descriptors need to be corrected in Bld 1 and 2; Blding 2 office duct detector discriptor identified device as being in building 4; contractor to check all induct smoke detectors descriptors in B 1 and 2 for accuarcy before next inspection; B2 4th floor riser room inaccessible due to malfunctioning lock on door; B1 basement riser room device descriptors to identify location of devices in basement; B4 basement pull station descriptor identifies device being on 1st floor; B3 notification appliances on 1st floor near main lobby not in synch.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Froese
|
Miscellaneous action | | | 2/4/2020 | | DONE |
|
|
|
2-3-20: Emailed Bill Clark the upgrade requirements for new panel replacement. He responded to indicate that he was in the process of meeting them.
2-3-20: Rob Ahten called to ask if the original panel brand and model were installed, would the upgrade still be required. I informe him no, unless the new panel permitted by Apex was signed off. If it had been signed off, it would be considered a change and upgrades would be required.
|
Application received | | | 1/30/2020 | | DONE |
|
|
|
Application submitted via PDS Online on Jan 30 2020 11:34AM
|
Plan assigned to (Lee) | 1/30/2020 | | 1/30/2020 | | DONE |
Lee G Meredith
|
|
|
|
Intake Approval | | | 1/30/2020 | | PASS |
|
|
|
|
1st review completed | | | 1/30/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 1/30/2020 | | 1/30/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 1/30/2020 | | DONE |
|
|
|
Quick permit passed. No review comments or drawing for emergency fire alarm panel replacement.
|
Permit Ready to Issue | | | 1/30/2020 | | DONE |
|
|
|
met
|
Issue and Print Permit | | | 1/30/2020 | | DONE |
|
|
|
|