Permit Information
Permit NumberFIR20-00069
StatusFinaled
Name APEX INTEGRATED SECURITY SOLUTIONS
Site Address 3075 W CRESCENT RIM DR
Project NameCRESCENT RIM FACP REPLACEMENT
Customer Number 
ePlanReviewYes
Description
PLAN MOD 2/7/20. Change FACP panel back to the original model to avoid upgrade requirements. Crescent Rim FACP Replacement scope of work is to replace the existing main FACP panel due to existing power failure condition. The existing Silent Knight Model 5820 addressable panel will be replaced with a new Silent Knight Model 6820 Addressable panel. This panel serves the entire Crescent Rim Condominium consisting of 4 apartment buildings within the complex.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/11/20202/12/20202/12/2020APASS
DetailsTroy Cobbley
Permit finaled.

Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
Plan assigned to (Lee)2/7/2020 2/10/2020 DONE
DetailsLee G Meredith
plan mod
1st review completed  2/10/2020 DONE
Alarm Plan Check2/10/2020 2/10/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  2/10/2020 DONE
Quick permit plan mod passed

Fees include 2 hours of review / coordination time at $65 per hour and 3 hours of inspection time at $55 per hour for temporarily installed 6820 fire alarm panel. $130 + $165 = $295 total permit fee.
Permit Ready to Issue  2/10/2020 DONE
plan mod passed
Issue and Print Permit  2/10/2020 DONE
Plan Modification Accepted  2/7/2020 DONE
Dante from Apex requested a plan mod workflow
INSP-Final Inspection2/6/20202/7/20202/6/2020ACANC
DetailsTroy Cobbley
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Thursday, February 06, 2020.
INSP-Final Inspection2/5/20202/6/20202/6/2020AFAIL
DetailsGreg Ruxton
Permit failed based on noted deficiencies: induct smoke detector descriptors need to be corrected in Bld 1 and 2; Blding 2 office duct detector discriptor identified device as being in building 4; contractor to check all induct smoke detectors descriptors in B 1 and 2 for accuarcy before next inspection; B2 4th floor riser room inaccessible due to malfunctioning lock on door; B1 basement riser room device descriptors to identify location of devices in basement; B4 basement pull station descriptor identifies device being on 1st floor; B3 notification appliances on 1st floor near main lobby not in synch.




Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Froese
Miscellaneous action  2/4/2020 DONE
2-3-20: Emailed Bill Clark the upgrade requirements for new panel replacement. He responded to indicate that he was in the process of meeting them.
2-3-20: Rob Ahten called to ask if the original panel brand and model were installed, would the upgrade still be required. I informe him no, unless the new panel permitted by Apex was signed off. If it had been signed off, it would be considered a change and upgrades would be required.
Application received  1/30/2020 DONE
Application submitted via PDS Online on Jan 30 2020 11:34AM
Plan assigned to (Lee)1/30/2020 1/30/2020 DONE
DetailsLee G Meredith
Intake Approval  1/30/2020 PASS
1st review completed  1/30/2020 DONE
Alarm Plan Check1/30/2020 1/30/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  1/30/2020 DONE
Quick permit passed. No review comments or drawing for emergency fire alarm panel replacement.
Permit Ready to Issue  1/30/2020 DONE
met
Issue and Print Permit  1/30/2020 DONE