Permit Information
Permit NumberFIR20-00105
StatusIssued
Name PROTEX
Site Address 10255 W OVERLAND RD
Project NameSt. Al's Outpatient Clinic
Customer Number 
ePlanReviewYes
Description
Install code-compliant fire alarm system for the purposes of sprinkler monitoring. This work is associated with building permit BLD19-04518.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
CHANGE STATUS TO (ISS)  4/29/2020 DONE
Plan assigned to (Lee)4/23/2020 4/24/2020 DONE
DetailsLee G Meredith
as built -update the reser for the addition of an addressable module for the pressure switch.
Intake Approval  4/24/2020 PASS
1st review completed  4/24/2020 DONE
Alarm Plan Check4/24/2020 4/24/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  4/24/2020 DONE
Corrected as built.
Permit Ready to Issue  4/24/2020 DONE
**AS BUILT - DO NOT REISSUE**
Plan resubmittals received  4/23/2020 DONE
as built request by Hailey Ahten see Doc email.
INSP-Final Inspection4/21/20204/22/20204/22/2020APART
DetailsTroy Cobbley
A temp for fire alarm until the plans are submitted showing the added/changed module on the low air switch. All devices tested ok.

Contact is Davis. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection4/20/20204/21/20204/21/2020AFAIL
DetailsTroy Cobbley
Actually went to the project site twice today. The first trip the descripters from the device to the panel did not match. Low air came in as an alarm and rang the bell. Came back the second time and the monitoring company descriptors do not match. Will need to reschedule for tomorrow and a re-inspection fee has been applied. Contact is Davis. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan assigned to (Lee)4/17/2020 4/20/2020 DONE
DetailsLee G Meredith
as builts
1st review completed  4/20/2020 DONE
Alarm Plan Check4/20/2020 4/20/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  4/20/2020 DONE
As built - No fee. Previous as built submittal did not show the stamp on one of the drawings.
Permit Ready to Issue  4/20/2020 DONE
as built approved (stamped drawing that was missed in the last as built per LGM)
CHANGE STATUS TO (ISS)  4/20/2020 DONE
INSP-Final Inspection4/17/20204/17/20204/17/2020PFAIL
DetailsTroy Cobbley
The signal reports show a different designation for alarms than what is tested, old fire alarm devices need removed, the facp installed does not match the facp submitted, the basement plan has no stamp on it, the riser sheet was not provided. No devices tested.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan resubmittals received  4/17/2020 DONE
Morgan with protex opening up for asbuilts
CHANGE STATUS TO (ISS)  4/17/2020 DONE
Plan resubmittals received  4/16/2020 DONE
Hailey from Protex requesting to open workflow for asbuilts
Plan assigned to (Lee)4/16/2020 4/16/2020 DONE
DetailsGabe Brenner
as builts
1st review completed  4/16/2020 DONE
Alarm Plan Check4/16/2020 4/16/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  4/16/2020 DONE
As built - No fee.
Permit Ready to Issue  4/16/2020 DONE
**DO NOT REISSUE - AS BUILT**
Permit Ready to Issue  2/19/2020 DONE
met
Issue and Print Permit  2/19/2020 DONE
Plan assigned to (Lee)2/18/2020 2/18/2020 DONE
DetailsLee G Meredith
Intake Approval  2/18/2020 PASS
1st review completed  2/18/2020 DONE
Alarm Plan Check2/18/2020 2/18/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  2/18/2020 DONE
Passed with review comments.
Application received  2/13/2020 DONE
Application submitted via PDS Online on Feb 13 2020 1:55PM