INSP-Final Inspection | 7/30/2020 | 7/31/2020 | 7/31/2020 | A | PASS |
Troy Cobbley
|
|
|
verified function of the new voice evac hand set.
ermit finaled. Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster
|
INSP-Final Inspection | 7/29/2020 | 7/30/2020 | 7/30/2020 | A | CANC |
Jim Page
|
|
|
Inspection ws suppose to be scheduled for 31JULY2020 per conversation with point of contact, this request is cancelled.
Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster
|
Plan assigned to (Lee) | 6/2/2020 | | 6/3/2020 | | DONE |
Lee G Meredith
|
|
|
As built # 3
|
Intake Approval | | | 6/3/2020 | | PASS |
|
|
|
|
1st review completed | | | 6/3/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 6/3/2020 | | 6/3/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 6/3/2020 | | DONE |
|
|
|
Plan mod passed. $65 minim review fee.
|
Permit Ready to Issue | | | 6/3/2020 | | DONE |
|
|
|
plan mod
|
CHANGE STATUS TO (ISS) | | | 6/3/2020 | | DONE |
|
|
|
|
Plan resubmittals received | | | 6/2/2020 | | DONE |
|
|
|
as built per Rita
|
INSP-Final Inspection | 5/19/2020 | 5/20/2020 | 5/20/2020 | A | PART |
Jim Page
|
|
|
Inpsection complete per NFPA72, city approved drawings to be updated for minor corrections before permit can be finaled. Possible addition of EVS-LOC in office area to be added to city approved drawings and installed at a later date. Fire alarm is complete for 90 day TCO.
Phone #: ###-#### Inspection requested via web by Ken Webster: Coordinated for 9AM with Jim Page
|
INSP-Final Inspection | 5/18/2020 | 5/19/2020 | 5/19/2020 | P | CANC |
Jim Page
|
|
|
Rescheduled for 20MAY2020 for completion of walkthrough items, this request is cancelled.
Phone #: ###-#### Inspection requested via web by Ken Webster
|
INSP-Final Inspection | 5/19/2020 | 5/19/2020 | 5/19/2020 | A | CANC |
Jim Page
|
|
|
Phone #: ###-#### Inspection requested via web by Ken Webster: Coordinated for 9AM with Jim Page
|
INSP-Final Inspection | 5/19/2020 | 5/19/2020 | 5/19/2020 | A | CANC |
Jim Page
|
|
|
Inpsection request was for a conference, this request is cancelled.
|
INSP-Conference | 5/19/2020 | 5/19/2020 | 5/19/2020 | A | DONE |
Jim Page
|
|
|
Performed walkthrough, items noted are: Strobes in gym lobby show 30cd on city approved plans, ceiling exceeds 20 feet, strobes will have to be increased. Nurses station strobe is overspaced plus one will need to be added for laydown area coverage. Kitchen hood causes coverage issues in kitchen area, stobe will need to be added for proper coverage. Device in mail room is overspaced, candela will need to be increased for proper coverage or relocate device. East corridor by stairs exceeds 20 feet, candela setting at 30cd does not provide proper coverage, candella will be increased to 75cd. Items noted will need to be reflected on city approved drawings before permit can be finaled.
|
Plan assigned to (Lee) | 5/13/2020 | | 5/18/2020 | | DONE |
Lee G Meredith
|
|
|
as builts
|
Intake Approval | | | 5/18/2020 | | PASS |
|
|
|
|
1st review completed | | | 5/18/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 5/18/2020 | | 5/18/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 5/18/2020 | | DONE |
|
|
|
As built - No fee.
|
Permit Ready to Issue | | | 5/18/2020 | | DONE |
|
|
|
as built approved
|
CHANGE STATUS TO (ISS) | | | 5/18/2020 | | DONE |
|
|
|
|
Plan resubmittals received | | | 5/13/2020 | | DONE |
|
|
|
Rita requested the workflow to be opened for as builts.
|
INSP-Alarm Testing | 4/6/2020 | 4/7/2020 | 4/7/2020 | A | PART |
Jim Page
|
|
|
Fire alarm testing is complete, fire sprinkler riser monitoring is tested/active.
clear // buck tom Phone #: ###-####
|
INSP-Final Inspection | 4/3/2020 | 4/6/2020 | 4/6/2020 | A | FAIL |
Troy Cobbley
|
|
|
No inspection test reports, flow switches and tampers are unhooked and when hooked back up there is a trouble signal also missing a resistor. No testing done. Inspection stopped.
cleared // Buck Phone #: ###-####
|
Plan resubmittals received | | | 3/6/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 3/6/2020 | | 3/6/2020 | | PASS |
Lee G Meredith
|
|
|
FA 0.0 corrections were not made.
|
PLANS TAKEN FRONT DESK ALARM | | | 3/6/2020 | | DONE |
|
|
|
Passed with review comments.
|
Permit Ready to Issue | | | 3/6/2020 | | DONE |
|
|
|
met
|
Issue and Print Permit | | | 3/6/2020 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 2/26/2020 | | 2/26/2020 | | DONE |
Lee G Meredith
|
|
|
|
Intake Approval | | | 2/26/2020 | | PASS |
|
|
|
|
1st review completed | | | 2/26/2020 | | FAIL |
|
|
|
Visible notification is inadequate in several areas. CO detection operations is incorrect. Revise and resubmit.
|
Application received | | | 2/25/2020 | | DONE |
|
|
|
Application submitted via PDS Online on Feb 25 2020 2:37PM
|