INSP-Final Inspection | 7/29/2020 | 7/29/2020 | 7/29/2020 | P | PASS |
Greg Ruxton
|
|
|
Fire Alarm Inspection complete and passed. All system components tested to include: flow and tamper switch monitoring, smoke detectors, pull station, NAC appliances and FACP function and reporting.
Anytime after 1pm Please Phone #: ###-#### Inspection requested via web by Matt Casey
|
INSP-Final Inspection | 7/28/2020 | 7/28/2020 | 7/28/2020 | P | CANC |
Troy Cobbley
|
|
|
Anytime after 1:30 pm please Phone #: ###-#### Inspection requested via web by Matt Casey
|
Issue and Print Permit | | | 3/4/2020 | | DONE |
|
|
|
|
Application received | | | 3/3/2020 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 3 2020 6:19AM
|
Plan assigned to (Lee) | 3/3/2020 | | 3/3/2020 | | DONE |
Lee G Meredith
|
|
|
|
Intake Approval | | | 3/3/2020 | | PASS |
|
|
|
|
1st review completed | | | 3/3/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 3/3/2020 | | 3/3/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 3/3/2020 | | DONE |
|
|
|
Passed with review comments.
|
Permit Ready to Issue | | | 3/3/2020 | | DONE |
|
|
|
met
|