INSP-Sprinkler Rough-in | 3/11/2020 | 3/12/2020 | 3/12/2020 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection for area of work is complete, area of work is approved for cover. Ceiling fan is installed in front of the fire place, sprinkler head next to fan is less than 3 foot away, if fan remains then sprinkler head must comply with 8.2.5 of the 2016 NFPA13D. Annual inspection on fire sprinkler system as well as backflow inspection will be required before this scope of work can be finaled.
christin Phone #: ###-####
|
Issue and Print Permit | | | 3/11/2020 | | DONE |
|
|
|
|
Intake Approval | | | 3/9/2020 | | PASS |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 3/9/2020 | | 3/9/2020 | | DONE |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 3/9/2020 | | 3/9/2020 | | PASS |
Mark Stumbaugh
|
|
|
|
1st review completed | | | 3/9/2020 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/9/2020 | | DONE |
Mark Stumbaugh
|
|
|
|
Permit Ready to Issue | | | 3/9/2020 | | DONE |
|
|
|
met
|
Application received | | | 3/6/2020 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 6 2020 11:03AM
|