INSP-Final Inspection | 4/15/2020 | 4/16/2020 | 4/16/2020 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled.
Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 4/15/2020 | 4/16/2020 | 4/16/2020 | A | PASS |
Troy Cobbley
|
|
|
Rough-in passed. Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Final Inspection | 4/14/2020 | 4/15/2020 | 4/15/2020 | A | CANC |
Troy Cobbley
|
|
|
Not ready for final.
Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 4/15/2020 | 4/15/2020 | 4/15/2020 | P | FAIL |
Troy Cobbley
|
|
|
The "DIsplay" area is ordinary hazard. Sprinklers are using the small room rule for light hazard. Sprinkler need to be respaced.
Gabe Garduno is the contact. Thank you!! Phone #: ###-#### Inspection requested via web by Stan Beus
|