Permit Information
Permit NumberFIR20-00266
StatusFinaled
Name NORTHWEST FIRE AND SECURITY
Site Address 7800 W USTICK RD Unit: 100
Project NameDR. PAIGE SCHMIDT T.I.
Customer Number 
ePlanReviewYes
Description
NEW SPRINKLER MONITORING PANEL. This work is associated with building permit BLD19-04891.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/11/20205/11/20205/11/2020PPASS
DetailsTroy Cobbley
Permit finaled.

please call 1/2 hour prior Phone #: ###-#### Inspection requested via web by Rick Groom
INSP-Final Inspection5/4/20205/5/20205/5/2020PFAIL
DetailsJim Page
No devices tested, horn strobes and pull stations from old fire alarm system are still in place, non-functioning fire alarm devices must be removed before final inspection can be completed, per installing contractor old devices in place are not integrated with the new fire alarm panel, also old devices are not compliant with the current NFPA72.

Please call 1/2hour prior Phone #: ###-#### Inspection requested via web by Rick Groom
Issue and Print Permit  4/22/2020 DONE
Plan assigned to (Lee)4/14/2020 4/14/2020 DONE
DetailsLee G Meredith
Intake Approval  4/14/2020 PASS
1st review completed  4/14/2020 DONE
Alarm Plan Check4/14/2020 4/14/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  4/14/2020 DONE
Passed as noted in the scope area of the review comments.
Permit Ready to Issue  4/14/2020 DONE
MET
Application received  4/13/2020 DONE
Application submitted via PDS Online on Apr 13 2020 1:52PM