Permit NumberFIR20-00353
StatusFinaled
Name WEBSTER FIRE PROTECTION
Site Address 9605 S EISENMAN RD
Project NameVerdi TI
Customer Number 
ePlanReviewYes
Description
Adding circulating fan shut down and RTU Monitoring to existing monitoring system. This work does not appear to be associated with a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/1/20207/1/20207/1/2020PPASS
DetailsTroy Cobbley
Permit finaled.
Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster
INSP-Final Inspection7/1/20207/1/20207/1/2020AFAIL
DetailsTroy Cobbley
Hvac unit did not immediatley shut down upon detection of smoke. Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster
INSP-Final Inspection6/29/20206/30/20206/30/2020PCANC
DetailsTroy Cobbley
Dialer not ready no inspection performed.

Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster
INSP-Final Inspection6/23/20206/23/20206/23/2020PCANC
DetailsJim Page
Monitoring was not set up correctly by monitoring permit holder, inspection will need to be rescheduled, this inspection is cancelled.

Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster
CHANGE STATUS TO (ISS)  6/23/2020 DONE
Plan assigned to (Lee)6/18/2020 6/22/2020 DONE
DetailsLee G Meredith
plan mod
Intake Approval  6/22/2020 PASS
1st review completed  6/22/2020 DONE
Alarm Plan Check6/22/2020 6/22/2020 DONE
DetailsLee G Meredith
Minimum $65 plan mod review fee due.
PLANS TAKEN FRONT DESK ALARM  6/22/2020 DONE
Plan mod passed. No additional review comments.
Permit Ready to Issue  6/22/2020 DONE
met
Plan Modification Accepted  6/18/2020 DONE
Rita called requesting a plan mod workflow
Plan assigned to (Lee)5/20/2020 5/20/2020 DONE
DetailsLee G Meredith
Miscellaneous action  5/20/2020 DONE
Emailed Rita to indicate drawings seem to be incorrect. No shut down relays shown on drawings, riser or product data.
Intake Approval  5/20/2020 PASS
Corrections have been made.
1st review completed  5/20/2020 DONE
Alarm Plan Check5/20/2020 5/20/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  5/20/2020 DONE
Passed. No written review comments provided.
Permit Ready to Issue  5/20/2020 DONE
Issue and Print Permit  5/20/2020 DONE
Application received  5/19/2020 DONE
Application submitted via PDS Online on May 19 2020 12:55PM