INSP-Final Inspection | 7/1/2020 | 7/1/2020 | 7/1/2020 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster
|
INSP-Final Inspection | 7/1/2020 | 7/1/2020 | 7/1/2020 | A | FAIL |
Troy Cobbley
|
|
|
Hvac unit did not immediatley shut down upon detection of smoke. Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster
|
INSP-Final Inspection | 6/29/2020 | 6/30/2020 | 6/30/2020 | P | CANC |
Troy Cobbley
|
|
|
Dialer not ready no inspection performed.
Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster
|
INSP-Final Inspection | 6/23/2020 | 6/23/2020 | 6/23/2020 | P | CANC |
Jim Page
|
|
|
Monitoring was not set up correctly by monitoring permit holder, inspection will need to be rescheduled, this inspection is cancelled.
Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster
|
CHANGE STATUS TO (ISS) | | | 6/23/2020 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 6/18/2020 | | 6/22/2020 | | DONE |
Lee G Meredith
|
|
|
plan mod
|
Intake Approval | | | 6/22/2020 | | PASS |
|
|
|
|
1st review completed | | | 6/22/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 6/22/2020 | | 6/22/2020 | | DONE |
Lee G Meredith
|
|
|
Minimum $65 plan mod review fee due.
|
PLANS TAKEN FRONT DESK ALARM | | | 6/22/2020 | | DONE |
|
|
|
Plan mod passed. No additional review comments.
|
Permit Ready to Issue | | | 6/22/2020 | | DONE |
|
|
|
met
|
Plan Modification Accepted | | | 6/18/2020 | | DONE |
|
|
|
Rita called requesting a plan mod workflow
|
Plan assigned to (Lee) | 5/20/2020 | | 5/20/2020 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 5/20/2020 | | DONE |
|
|
|
Emailed Rita to indicate drawings seem to be incorrect. No shut down relays shown on drawings, riser or product data.
|
Intake Approval | | | 5/20/2020 | | PASS |
|
|
|
Corrections have been made.
|
1st review completed | | | 5/20/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 5/20/2020 | | 5/20/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 5/20/2020 | | DONE |
|
|
|
Passed. No written review comments provided.
|
Permit Ready to Issue | | | 5/20/2020 | | DONE |
|
|
|
|
Issue and Print Permit | | | 5/20/2020 | | DONE |
|
|
|
|
Application received | | | 5/19/2020 | | DONE |
|
|
|
Application submitted via PDS Online on May 19 2020 12:55PM
|