INSP-Final Inspection | 7/29/2020 | 8/4/2020 | 8/4/2020 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled.
Please call 20-30 minutes prior to inspection. You will be meeting technician Justin Volquardsen in site. Phone #: ###-#### Inspection requested via web by jason petty
|
INSP-Final Inspection | 7/6/2020 | 7/8/2020 | 7/8/2020 | A | FAIL |
Troy Cobbley
|
|
|
Provide as-builts/plan mod fhowing the correct zone ayout and the installation of the heat instead of a smoke detector. The detector needs to be mounted with in 12" of the deck. Need map, knox box and correct size batteries installed. Need to test the flow switch and heat detector.
Please call 20-30 minutes prior to inspection. You will be meeting technician Justin Volquardsen on site. Phone #: ###-#### Inspection requested via web by jason petty
|
Application received | | | 5/21/2020 | | DONE |
|
|
|
Application submitted via PDS Online on May 21 2020 10:28AM
|
Plan assigned to (Lee) | 5/21/2020 | | 5/21/2020 | | DONE |
Lee G Meredith
|
|
|
|
Intake Approval | | | 5/21/2020 | | PASS |
|
|
|
|
1st review completed | | | 5/21/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 5/21/2020 | | 5/21/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 5/21/2020 | | DONE |
|
|
|
Passed with review comments.
|
Permit Ready to Issue | | | 5/21/2020 | | DONE |
|
|
|
|
Issue and Print Permit | | | 5/21/2020 | | DONE |
|
|
|
|