Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR20-00380
StatusIssued
Name CRANE ALARM SERVICE
Site Address 4719 S MARKET ST
Project NameMarket Street
Customer Number 
ePlanReviewYes
Description
FACP replacement due to 4 duct detectors added for the TI. System includes sprinkler monitoring, amonia monitoring, smoke detection for door holder release, and duct detection. This work does not appear to be associated with a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/28/20208/4/20208/4/2020PFAIL
DetailsJim Page
Fire bell by FDC rang only with flow from the wet system in the fire pump room, bell needs to ring during water flow on all of the other sprinkler systems throughout the building as well. Pull stations exceed 48 inches off of finish floor. PIV tamper could not be tested on the northwest side of building, PIV handle is seized and would not turn. Demo old NAC panel that is no longer in service. Tamper valve on hose valves from riser 5 needs to be connected per IFC 903.4. Provide conduit connector for riser 5 OS&Y tamper as discussed. Tamper switch on riser 6 would not stay clear, was determined that switch will need to be replaced. Other than items noted fire sprinkler monitoring is complete.

Crane Alarm and sprinkler contractor will be on site at 12:00PM Phone #: ###-#### Inspection requested via web by Fire Scheduler
INSP-Conference7/24/20207/24/20207/24/2020ADONE
DetailsJim Page
A fire sprinkler technician will be required for fire alarm inspection due too the type of sprinkler systems being monitored. Building has diesel fire pump, multiple dry systems and pre-action systems. Permit is for fire alarm system replacement so fire sprinkler riser monitoring will need to be tested.
INSP-Final Inspection7/23/20207/24/20207/24/2020PCANC
DetailsJim Page
Final inspection cancelled per conversation with point of contact, will be rescheduled with requirements listed in the scheduled conference.

Fire Alarm Final for Market St. Inspection for mid morning 11:30 AM Phone #: ###-#### Inspection requested via web by Fire Scheduler
INSP-Final Inspection7/22/20207/23/20207/23/2020ACANC
DetailsJim Page
Phone #: ###-#### >> Inspection requested via web by Fire Scheduler Inspection cancelled from web by: Fire Scheduler
Issue and Print Permit  6/2/2020 DONE
Plan assigned to (Lee)6/1/2020 6/1/2020 DONE
DetailsLee G Meredith
Intake Approval  6/1/2020 PASS
1st review completed  6/1/2020 DONE
Alarm Plan Check6/1/2020 6/1/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/1/2020 DONE
Passed with review comments.
Permit Ready to Issue  6/1/2020 DONE
Application received  5/31/2020 DONE
Application submitted via PDS Online on May 31 2020 2:29PM