Permit Information
Permit NumberFIR20-00404
StatusFinaled
Name ALL VALLEY FIRE INSPECTIONS AND SER
Site Address 898 W GOWEN RD
Project NameNorco Fill Plant Paintbooth
Customer Number 
ePlanReviewYes
Description
To install 3 new remote fire alarm pull stations by all 3 exits of the paint booth area room 120. New addressable relays are to be installed to open the paint booth interlock thus shutting the paint booth process off. The new paint booth will have a fire sprinkler control valve relocated. This will be monitored. This work is associated with building permit BLD20-01585.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/6/20207/6/20207/6/2020PPASS
DetailsJim Page
Previously noted item has been corrected, final fire alarm inspection is complete.

This is for the fire alarm permit. The Paint Booth Interlock has been modified to shutdown the conveyor and heat tunnel. Phone #: ###-#### Inspection requested via web by Jason Heath
INSP-Final Inspection6/30/20207/2/20207/2/2020AFAIL
DetailsJim Page
Conveyor line did not shut down on fire alarm activation as stated in building permit fire code review comments.

I am trying to get Rick from TVFP at the same time as my FINAL. Please call me early as possible on Thursday so I can get Rick from TVFP on board
Phone #: ###-#### Inspection requested via web by Jason Heath
Issue and Print Permit  6/18/2020 DONE
Plan assigned to (Lee)6/17/2020 6/17/2020 DONE
DetailsLee G Meredith
Intake Approval  6/17/2020 PASS
1st review completed  6/17/2020 DONE
Alarm Plan Check6/17/2020 6/17/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/17/2020 DONE
Passed with review comments.
Permit Ready to Issue  6/17/2020 DONE
Application received  6/9/2020 DONE
Application submitted via PDS Online on Jun 9 2020 2:50PM