INSP-Final Inspection | 8/5/2020 | 8/6/2020 | 8/6/2020 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled.
Please contact Mark McMillian to verify start time. ###-#### Thank you. Phone #: ###-#### Phone #: ###-#### Inspection requested via web by James Schofield
|
INSP-Final Inspection | 8/5/2020 | 8/5/2020 | 8/5/2020 | P | CANC |
Troy Cobbley
|
|
|
Please contact Mark McMillian to verify start time. ###-#### Thank you. Phone #: ###-#### >> Inspection requested via web by James Schofield Inspection cancelled from web by: James Schofield
|
Issue and Print Permit | | | 7/10/2020 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/8/2020 | | DONE |
|
|
|
|
Intake Approval | | | 7/8/2020 | | PASS |
|
|
|
|
1st review completed | | | 7/8/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 7/8/2020 | | 7/8/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/8/2020 | | DONE |
|
|
|
Passed with review comments and drawing notes.
|
Permit Ready to Issue | | | 7/8/2020 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 7/1/2020 | | 7/1/2020 | | DONE |
Lee G Meredith
|
|
|
|
Intake Approval | | | 7/1/2020 | | FAIL |
|
|
|
Product data missing, design does not match engineered drawings, requested design criteria from JCI for reasoning behind 1 of 5 classrooms getting a smoke/CO detector. Engineer of Record review not provided.
|
Application received | | | 6/24/2020 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 24 2020 4:28PM
|