INSP-Final Inspection | 7/8/2020 | 7/9/2020 | 7/9/2020 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled by Greg. Retest on the hood fire suppression system. STEAM KETTLES ARE ELECTRIC!!!! NO GAS REQUIRED!! Thank you! Phone #: ###-#### Inspection requested via web by Don Kartchner
|
INSP-Final Inspection | 7/7/2020 | 7/8/2020 | 7/8/2020 | A | PASS |
Greg Ruxton
|
|
|
Hood functions tested to include shutdown of electrical circuits, puff test, pull station, thermal link activation and location of Class K FE.
At time of inspection no gas fired or grease and smoke generating appliances were installed under the hood. Gas lines capped off for possible future expansion. All currently installed appliances electric and consist of two steam kettles, an oven and a steam cabinet. Any future additions or changes of hood applianc(s) will require a seperate permit.
Final inspection of a new Ansul R102 6.0 gallon fire suppression system. Phone #: ###-#### Inspection requested via web by Don Kartchner
|
Issue permit | | | 7/7/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/7/2020 | | DONE |
|
|
|
This permit was created on the web by Don Kartchner
|