INSP-Sprinkler Rough-in/Hydro | 10/25/1999 | 10/27/1999 | 10/27/1999 | P | NR |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/25/1999 at 08:32:49. Contact: ###-####. Contractor will reschedule
|
Inspection Record Card- Bld | 9/27/1999 | 9/27/1999 | 9/27/1999 | | DONE |
|
|
|
|
Issue permit | | | 9/27/1999 | | DONE |
|
|
|
|
Plans/Appl Taken to Front Desk | | | 9/17/1999 | | PASS |
|
|
|
|
Fire Sprinkler Plan Check | | | 9/16/1999 | | PASS |
|
|
|
|
Telephone call | | | 9/13/1999 | | PEND |
|
|
|
Jeff indicated they sent the wrong (existing) plan.
|
Telephone Call | | | 9/10/1999 | | PEND |
|
|
|
Called Jeff (designer). Cannot follow calculations out of the basement to the fifth floor with nodes provided. Said he will get back with me Monday 9/13/1999 with reply.
|
Fire Sprinkler Plan Check | | | 9/9/1999 | | FAIL |
|
|
|
Calculation input did not match plans.
|
Application received | | | 9/3/1999 | | PASS |
|
|
|
|
Issue permit | | | | | PEND |
|
|
|
|