Permit Information
Permit NumberFIR99-00473
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 7009 W FRANKLIN RD
Project NameSPR BISHOP KELLY - GYM.
Customer Number 
ePlanReviewNo
Description
BISHOP KELLY HIGHSCHOOL GYMNASIUM AND NEW CLASSROOM ADDITION * 35,117 SQ. FT. TWO STORY GYMNASIUM BUILDING. CONSTRUCTION WILL BE TYPES II-1HR WITH SPRINNKLER SUBSTIITUTION AND TYPE V-1HR WITH A TWO HOUR AREA SEPARATION WALL BETWEEN THE MAIN GYM AND THE WRESTLING ROOM. OTHER WORK INCLUDES UNDERGROUND SUPPLY PER APPROVED PLANS AND ATTACHMENTS. CUP98-0130 PC#183-99 (GRADING UNDER PERMIT BLD99-0681 WITH ITS OWN SET OF PLANS). FIRE SPRINKLERS USED FOR ONE-HOUR SUBSTITUTION NOT AREA. BUILDING HAS 28,493 SQ. FT. ON THE FIRST FLOOR WITH 6,624 SQ. FT. ON THE SECOND FLOOR. CLASSROOMS ARE 2,973 SQ. FT. ONE STORY, TYPE VN FULLY FIRE SPRINKLERED CLASSROOM ADDITION TO THE EXISTING HIGHSCHOOL CLASSROOM WING. ALL WORK IS PER APPROVED PLANS AND ATTACHMENTS, CUP98-0130, PC#184-99. FIRE SPRINKLERS ARE USED FOR AREA INCREASE.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled4/19/20014/19/20014/19/2001APASS
DetailsJoe Tawney
Added by Inspector: 406 On 4/19/2001 11:38:47 AM
INSP-Final Inspection3/6/20003/6/20003/6/2000PFAIL
DetailsJoe Tawney
Tracy ###-#### around 2 Underground hydro test fail. 3/7/00 8:45:58 AM
INSP-Supply line flush3/6/20003/6/20003/6/2000APART
DetailsJoe Tawney
ok on supply line flush.
Inspection Record Card- Bld9/21/19999/21/19999/21/1999 DONE
Issue permit  9/21/1999 DONE
Fire Sprinkler Plan Check  9/20/1999 PASS
Plans/Appl Taken to Front Desk  9/20/1999 PASS
Telephone call  9/16/1999 FAIL
Indicated problem of density to area calculated per head problem and to verify with correct calculations.
Telephone call  9/16/1999 PEND
Brad kilburn called and indicated that the Gym area calculations were still good on remaining cushion, but the wrestling room is difficiant and requires line and main changes. Will submit changes of plans and calculations.
Fire Sprinkler Plan Check  9/13/1999 FAIL
Remote density ot sqauare feet per sprinkler head areas do not match calculations in both the Gym and Wrestling room.
Application received  9/7/1999 PASS