DOC - Permit Finaled | 4/19/2001 | 4/19/2001 | 4/19/2001 | A | PASS |
Joe Tawney
|
|
|
Added by Inspector: 406 On 4/19/2001 11:38:47 AM
|
INSP-Final Inspection | 3/6/2000 | 3/6/2000 | 3/6/2000 | P | FAIL |
Joe Tawney
|
|
|
Tracy ###-#### around 2 Underground hydro test fail. 3/7/00 8:45:58 AM
|
INSP-Supply line flush | 3/6/2000 | 3/6/2000 | 3/6/2000 | A | PART |
Joe Tawney
|
|
|
ok on supply line flush.
|
Inspection Record Card- Bld | 9/21/1999 | 9/21/1999 | 9/21/1999 | | DONE |
|
|
|
|
Issue permit | | | 9/21/1999 | | DONE |
|
|
|
|
Fire Sprinkler Plan Check | | | 9/20/1999 | | PASS |
|
|
|
|
Plans/Appl Taken to Front Desk | | | 9/20/1999 | | PASS |
|
|
|
|
Telephone call | | | 9/16/1999 | | FAIL |
|
|
|
Indicated problem of density to area calculated per head problem and to verify with correct calculations.
|
Telephone call | | | 9/16/1999 | | PEND |
|
|
|
Brad kilburn called and indicated that the Gym area calculations were still good on remaining cushion, but the wrestling room is difficiant and requires line and main changes. Will submit changes of plans and calculations.
|
Fire Sprinkler Plan Check | | | 9/13/1999 | | FAIL |
|
|
|
Remote density ot sqauare feet per sprinkler head areas do not match calculations in both the Gym and Wrestling room.
|
Application received | | | 9/7/1999 | | PASS |
|
|
|
|