Permit Information
Permit NumberFIR99-00497
StatusFinaled
Name DON WELAND
Site Address 5482 N QUAIL SUMMIT PL
Project Name 
Customer Number 
ePlanReviewNo
Description
To fire sprinkler per NFPA 13D a 4,044 sq. ft. two story single family dwelling. Sprinkler conditions shall include the protection along the attached 1,118 sq.ft. three car garage. Contractor indicates point of connection is in the house, but shall be verified per installation at point of connection to existing street supply. All engineering and attached requirement lists. (1st floor 2858 sq. ft.)(2nd floor 1186 sq. ft.) This lot is located within a hillside area and is subject to the hillside ordinance. Unless otherwise approved by the Boise City Fire Department, all lots shall be fitted with an NFPA 13D fire sprinkler system including all closets, bathrooms and attached garages. Class "A" roof system to be installed. PC #455 DJO CU #94-90 DJO
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/19/20019/19/20019/19/2001PPASS
DetailsJoe Tawney
Added by Inspector: 406 On 9/19/2001 12:58:59 PM
DOC - Permit Finaled9/19/20019/19/20019/19/2001PPASS
DetailsJoe Tawney
Finaled by inspector at 9/19/2001 12:59:04 PM
INSP-Final Inspection10/6/199910/7/199910/7/1999APART
DetailsJoe Tawney
SHELLY ###-#### FN FIRE ok on hydro test
INSP-Sprinkler Rough-in10/7/199910/5/199910/5/1999PPART
DetailsJoe Tawney
okay on sprinkler spacing ok to cover 1st floor only
Inspection Record Card- Bld10/1/199910/1/199910/1/1999 DONE
Telephone call  10/1/1999 DONE
Called Shilo Automatic ###-####
Fire Sprinkler Plan Check  9/27/1999 FAIL
Need calculations including meter loss, etc. Include questions on ceiling slopes; standard NFPA 13 Chapter 6 equirements?
Telephone Call  9/27/1999 FAIL
Indicated problems and requests to designer (Don) and what was requested. Response was positive. Facility is all flat ceilings.
1. Locate node D-1 on the plans.
2. Include meter in calculation. Verify size first, and pipe size supplying it.
3. Remove "no sprinklers in bathroom, closet, pantry," etc. notes. (Are Required).
5. Remove general note # 10. (Not related).
Application received  9/20/1999 PASS
INSP-Sprinkler Rough-in10/4/199910/5/1999 A 
DetailsJoe Tawney
Shelly ###-####
INSP-Sprinkler Rough-in10/4/199910/4/1999 P 
DetailsJoe Tawney
SHELLY-- ###-#### R/I
Issue permit