INSP-Final Inspection | 4/8/2002 | 4/8/2002 | 4/8/2002 | A | PASS |
Troy Cobbley
|
|
|
Fire sprinklers finaled. Contractor stated all items on the correction list had been corrected and verified by Joe Tawney.
|
DOC - Permit Finaled | 4/8/2002 | 4/8/2002 | 4/8/2002 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 4/8/2002 11:35:32 AM
|
Issue permit | | | 10/25/1999 | | DONE |
|
|
|
|
Inspection Record Card- Bld | 10/21/1999 | 10/21/1999 | 10/21/1999 | | DONE |
|
|
|
|
Telephone call | | | 10/21/1999 | | DONE |
|
|
|
###-####
|
Telephone call | | | 10/21/1999 | | DONE |
|
|
|
###-#### Commercial Fire
|
Fire Sprinkler Plan Check | | | 10/20/1999 | | PASS |
|
|
|
|
Plans/Appl Taken to Front Desk | | | 10/20/1999 | | PASS |
|
|
|
|
Fire Sprinkler Plan Check | | | 10/19/1999 | | FAIL |
|
|
|
Four previous items still not clarified or resolved. Alarming note request added in clarification to be tied into smoke detection system, since company may miss note on review.
|
Fire Sprinkler Plan Check | | | 10/15/1999 | | FAIL |
|
|
|
Meter not included in calculations, problems with nodes/clarifications, Head spacing in garage is overspaced, more information on backflow preventer, hanger detail needed on plans, pipe not identified on plans, clarification on elevations/sectional, need to calculate single head, need data on calculations indicating safety margin.
|
Application received | | | 10/8/1999 | | PASS |
|
|
|
|