Permit Information
Permit NumberFIR99-00640
StatusFinaled
Name TREASURE VALLEY FIRE
Site Address 7990 W OVERLAND RD
Project NameSPR LOWE'S
Customer Number 
ePlanReviewNo
Description
LOWE'S * TO INSTALL A FIRE SPRINKLER SYSTEM WITH FIRE PUMP, A NEW 169,985 SQ. FT., ONE STORY RETAIL HARDWARE AND GARDEN STORE AND RELATED. THIS BUILDING IS BEING CONSTRUCTED OF A CONCRETE SLAB FLOOR, CONCRETE MASONRY WALLS AND STEEL FRAME ROOF SYSTEM. THIS BUILDING IS FULLY FIRE SPRINKLERED. THE SPRINKLERS ARE BEING USED FOR UNLIMITED AREA. ALL INSTALLATIONS PER THE APPROVED PLANS AND ATTACHED REQUIREMENT LIST.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled5/9/20015/9/20015/9/2001PPASS
DetailsJoe Tawney
Finaled by inspector at 5/9/2001 2:47:52 PM
INSP-Final Inspection3/20/20003/20/20003/20/2000PPART
DetailsJoe Tawney
###-#### Reinsp. ok on alarm & sprinkler systems 3/21/00 9:25:07 AM
INSP-Final Inspection3/17/20003/17/20003/17/2000PFAIL
DetailsJoe Tawney
Final fail mount fire ext. fax of alarm signals.
INSP-Final Inspection3/10/20003/10/20003/10/2000PFAIL
DetailsJoe Tawney
don ###-#### pager Alarm test fail reprogram 2 floor switches on dry pipe systems & tamper switches on osty valves. 3/14/00 11:21:42 AM
INSP-Sprinkler Rough-in/Hydro3/6/20003/7/20003/7/2000PPART
DetailsJoe Tawney
###-#### DON\\PUMP TEST Ok on pump generator test. On emergency light test gen. to start & pick up load in 10 sec. or less. 3/8/00 9:57:20 AM
INSP-Final Inspection2/28/20002/29/20002/29/2000PPART
DetailsJoe Tawney
Don ###-#### pager Ok on test of booster fire pump. 3/1/00 11:17:57 AM
INSP-Sprinkler Rough-in/Hydro2/25/20002/25/20002/25/2000PPART
DetailsJoe Tawney
###-#### Ok hydro test of system #4 drysystem. 2/28/00 2:16:55 PM
INSP-Sprinkler Rough-in/Hydro2/24/20002/24/20002/24/2000PPART
DetailsJoe Tawney
###-#### don\\lowes hardware Ok on underground hydro & aboce ground hydro on systems #1,2,3,4 & 5 ok on partial R/I. 2/25/00 9:39:40 AM
INSP-Supply line flush2/22/20002/22/20002/22/2000PPART
DetailsJoe Tawney
Scheduled by a contractor via Hello! on 02/22/2000 at 08:57:50. Contact: ###-####. Ok to cover sprinklers in rear rooms. 2/23/00 11:37:15 AM
Sprinkler Plan Check2/14/2000 2/22/2000 PASS
DetailsBill Alexander
Resubmittal on revised racks spacing and over head system.
Telephone call  2/22/2000 DONE
talked to recp to verify plans are ready
INSP-Supply line flush1/31/20001/31/20001/31/2000PPASS
DetailsJoe Tawney
Mike ###-####. underground flush only 2/1/00 8:33:28 AM
INSP-Conference1/20/20001/20/20001/20/2000PPART
DetailsJoe Tawney
Conf. with Bryan, cont. regarding possible sprinkler head obstructions.
INSP-Sprinkler Rough-in1/18/20001/18/20001/18/2000PFAIL
DetailsJoe Tawney
bryan ###-#### Not ready for R/I inspection. 1/19/00 1:36:19 PM
Issue permit  12/21/1999 DONE
Inspection Record Card- Bld12/20/199912/20/199912/20/1999 DONE
Sprinkler Plan Check12/13/1999 12/20/1999 PASS
Miscellaneous action  12/20/1999 PASS
Plans taken to front desk for distribution.
Telephone call  12/20/1999 PASS
Faxed Review to Treasure Valley
Sprinkler Plan Check12/6/1999 12/6/1999 FAIL
MANY QUESTIONS ON NFPA INSTALLATION ISSUES AND CLARIFICATIONS REQUIRED. AN ISSUE WITH HAZARDOUS MATERIAL MANAGEMENT PLAN.
Telephone call  12/6/1999 FAIL
FAXED REVIEW TO TREASURE VALLEY.
Application received  12/3/1999 PASS
Application received  11/24/1999 FAIL
NEED HEADS, PUMP DATA SUBMITTALS
Miscellaneous action    PEND
PLANS TAKEN TO THE FRONT DESK
Case Summary     
Case Summary    PASS
DetailsBill Alexander
2nd Rack review