Permit Information
Permit NumberFIR99-00656
StatusFinaled
Name TREASURE VALLEY FIRE
Site Address 1001 E GOWEN RD
Project NameSPR SHOPKO DIST ADD
Customer Number 
ePlanReviewNo
Description
TO FIRE SPRINKLER A 134,000 SQUARE FOOT ADDITION TO THE SOUTH END OF THE EXISTING SHOPKO DISTRIBUTION CENTER WAREHOUSE ON AN EXISTING FOUNDATION CONSTRUCTED UNDER PERMIT BLD99-2009. THIS ADDITION IS CONSTRUCTED OF A CONCRETE SLAB FLOOR AND STEEL BUILDING FRAME. ALL WORK PER THE APPROVED PLANS AND ATTACHED REQUIREMENT LIST. THIS BUILDING IS FULLY FIRE SPRINKLERED, USING NFPA 13 1999 EDITION (ESFR HEADS). THE SPRINKLERS ARE USED FOR ALLOWABLE AREA INCREASE (UNLIMITED AREA). GRADING PERMIT BLD99-1982 **JWA**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled1/10/20021/10/20021/10/2002PPASS
DetailsRick Jackson
Finaled by inspector at 1/10/2002 2:53:18 PM
INSP-Final Inspection9/22/20009/22/20009/22/2000APASS
DetailsRick Jackson
Scheduled by Inspector: 409 On 9/22/2000
INSP-Sprinkler Rough-in/Hydro2/22/20002/22/20002/22/2000PPART
DetailsRick Jackson
hydro static test above ground Jim ###-#### pager/ hydro okay
INSP-Sprinkler Rough-in2/4/20002/7/20002/7/2000APART
DetailsRick Jackson
jim pager ###-####-r/i fire Fire risers not complete; tape on heads; earthquaking not complete.
Sprinkler Plan Check12/23/1999 1/13/2000 PASS
REVISED HOSE STATION LOCATIONS PROVIDED
Miscellaneous action  1/13/2000 PASS
Inspection Record Card- Bld12/14/199912/14/199912/14/1999 DONE
Telephone call  12/14/1999 DONE
Issue permit  12/14/1999 DONE
Telephone call  12/13/1999 PASS
VERIFIED THEY MAY HAVE POSSIBLE PROBLEMS WITH AUTOMATED RACKING FOR BLOCKAGE. VERIFIED THEY MAY HAVE PROBLEM WITH RADIANT HEATING SYSTEM.
Telephone call  12/13/1999 PASS
STILL NEEDED PUMP PERFORMANCE INFORMATION (GREG INDICATED IT WAS FAXED SATURDAY @ 5:00 A.M. TO ###-####). I DID NOT RECEIVE THE FAX?
Sprinkler Plan Check12/10/1999 12/13/1999 PASS
NEEDED PAGE 2 OF THE ESFR'S. DELAYED RESUBMITTALSS ON REVISING FIRE HOSE STATIONS. NEEDED PUMP DATA VERIFICATION ON LATES PERFORMANCE TEST (SINCE USING IT IN DESIGNING THE SYSTEM). NEEDED NODES USED IN CALCULATION ON PUMP PIPING.
Miscellaneous action  12/13/1999 PASS
PLANS TAKEN TO THE FRONT DESK.
Telephone call  12/10/1999 PASS
NEEDED PUMP DATA VERIFICATION ON LATES PERFORMANCE TEST (SINCE USING IT IN DESIGNING THE SYSTEM).
Telephone call  12/10/1999 PASS
NEEDED DELAYED SUBMITTALS ON FIRE HOSE STATIONS MEETING CLASS 2 SYSTEM.
Telephone call  12/9/1999 PASS
NEEDED NODES USED IN CALCULATION ON PUMP PIPING.
Application received  12/8/1999 PASS
Case Summary     
HOSE REVISION
Case Summary