DOC - Permit Finaled | 1/10/2002 | 1/10/2002 | 1/10/2002 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 1/10/2002 2:53:18 PM
|
INSP-Final Inspection | 9/22/2000 | 9/22/2000 | 9/22/2000 | A | PASS |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 9/22/2000
|
INSP-Sprinkler Rough-in/Hydro | 2/22/2000 | 2/22/2000 | 2/22/2000 | P | PART |
Rick Jackson
|
|
|
hydro static test above ground Jim ###-#### pager/ hydro okay
|
INSP-Sprinkler Rough-in | 2/4/2000 | 2/7/2000 | 2/7/2000 | A | PART |
Rick Jackson
|
|
|
jim pager ###-####-r/i fire Fire risers not complete; tape on heads; earthquaking not complete.
|
Sprinkler Plan Check | 12/23/1999 | | 1/13/2000 | | PASS |
|
|
|
REVISED HOSE STATION LOCATIONS PROVIDED
|
Miscellaneous action | | | 1/13/2000 | | PASS |
|
|
|
|
Inspection Record Card- Bld | 12/14/1999 | 12/14/1999 | 12/14/1999 | | DONE |
|
|
|
|
Telephone call | | | 12/14/1999 | | DONE |
|
|
|
|
Issue permit | | | 12/14/1999 | | DONE |
|
|
|
|
Telephone call | | | 12/13/1999 | | PASS |
|
|
|
VERIFIED THEY MAY HAVE POSSIBLE PROBLEMS WITH AUTOMATED RACKING FOR BLOCKAGE. VERIFIED THEY MAY HAVE PROBLEM WITH RADIANT HEATING SYSTEM.
|
Telephone call | | | 12/13/1999 | | PASS |
|
|
|
STILL NEEDED PUMP PERFORMANCE INFORMATION (GREG INDICATED IT WAS FAXED SATURDAY @ 5:00 A.M. TO ###-####). I DID NOT RECEIVE THE FAX?
|
Sprinkler Plan Check | 12/10/1999 | | 12/13/1999 | | PASS |
|
|
|
NEEDED PAGE 2 OF THE ESFR'S. DELAYED RESUBMITTALSS ON REVISING FIRE HOSE STATIONS. NEEDED PUMP DATA VERIFICATION ON LATES PERFORMANCE TEST (SINCE USING IT IN DESIGNING THE SYSTEM). NEEDED NODES USED IN CALCULATION ON PUMP PIPING.
|
Miscellaneous action | | | 12/13/1999 | | PASS |
|
|
|
PLANS TAKEN TO THE FRONT DESK.
|
Telephone call | | | 12/10/1999 | | PASS |
|
|
|
NEEDED PUMP DATA VERIFICATION ON LATES PERFORMANCE TEST (SINCE USING IT IN DESIGNING THE SYSTEM).
|
Telephone call | | | 12/10/1999 | | PASS |
|
|
|
NEEDED DELAYED SUBMITTALS ON FIRE HOSE STATIONS MEETING CLASS 2 SYSTEM.
|
Telephone call | | | 12/9/1999 | | PASS |
|
|
|
NEEDED NODES USED IN CALCULATION ON PUMP PIPING.
|
Application received | | | 12/8/1999 | | PASS |
|
|
|
|
Case Summary | | | | | |
|
|
|
HOSE REVISION
|
Case Summary | | | | | |
|
|
|
|