DOC - Permit Finaled | 12/7/2001 | 12/7/2001 | 12/7/2001 | P | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 12/7/2001 3:32:20 PM
|
INSP-Sprinkler Rough-in/Hydro | 3/13/2001 | 3/14/2001 | 3/14/2001 | P | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 03/13/2001 at 10:32:53. Contact: ###-####. see permit number FIR00-00123 for correct permit 3/14/2001 2:57:18 PM
|
INSP-Sprinkler Rough-in/Hydro | 11/16/2000 | 11/16/2000 | 11/16/2000 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 11/16/2000 4:00:25 PM ///not complete 11/16/2000 4:00:53 PM
|
INSP-Sprinkler Rough-in | 9/18/2000 | 9/21/2000 | 9/21/2000 | A | PART |
Rick Jackson
|
|
|
###-#### tested the fire pump; 500 gpm pump tested at 150, 100 percent and churn; flushed dry standpipe at roof outlet; alarms not complete and will retest for alarms when they are complete 9/21/2000 9:13:56 AM
|
INSP-Sprinkler Rough-in | 9/14/2000 | 9/18/2000 | 9/18/2000 | A | PART |
Rick Jackson
|
|
|
todd ###-#### hydro okay for standpipes, FDC 9/18/2000 9:33:38 AM
|
INSP-Sprinkler Rough-in | 9/7/2000 | 9/12/2000 | 9/12/2000 | P | FAIL |
Rick Jackson
|
|
|
TODD- ###-#### R/I hydro test of 2,3,4,5,6 and attic areas pass; r/i revealed attic area not covered, 6th floor has major deviations from plans requiring resubmittal, head painted on 2nd janitor room, dry standpipe needs pitch to ensire drainage 9/13/2000 11:06:22 AM
|
Issue permit | | | 2/7/2000 | | DONE |
|
|
|
|
Alarm Plan Check | 2/1/2000 | | 2/7/2000 | | PASS |
|
|
|
Revised calculations and clarifications submitted
|
Telephone call | | | 2/7/2000 | | PASS |
|
|
|
Faxed final review with instruction to attached the modified notes to site plan, etc. (Ref Grinnell Fax3 2/7/00)
|
Inspection Record Card- Bld | 2/1/2000 | 2/1/2000 | 2/1/2000 | | DONE |
|
|
|
|
Telephone call | | | 2/1/2000 | | DONE |
|
|
|
talked to nancy to verify plans are ready
|
Sprinkler Plan Check | 1/31/2000 | | 1/31/2000 | | PASS |
|
|
|
With Conditions attached to notes
|
Sprinkler Plan Check | 1/21/2000 | | 1/26/2000 | | FAIL |
|
|
|
Calculation problems.
|
Telephone call | | | 1/26/2000 | | FAIL |
|
|
|
Faxed review.
|
Sprinkler Plan Check | 12/23/1999 | | 12/23/1999 | | FAIL |
|
|
|
Lacking sufficiant pertinent information need to do a correctl review. Items required in NFPA 13 Chapter 6.
|
Application received | | | 12/15/1999 | | PASS |
|
|
|
|
Case Summary | | | | | |
|
|
|
|