GCB-Final | 3/28/2012 | 3/29/2012 | 3/29/2012 | A | PASS |
Mike Jordan
|
|
|
Jerry @ ###-####. All issues resolved. Structural final only ok.
|
GCB-Final | 3/27/2012 | 3/28/2012 | 3/28/2012 | P | FAIL |
Mike Jordan
|
|
|
Jerry @ ###-#### PM Inspection. Remove thumb turn from main entry door, provide sticker over main door "Yhis door to remain unlocked during bussiness hours" provide fire extinguishers, provide ada bathroom sign and post at required location.
|
GCB-Ceiling Grid | 3/15/2012 | 3/16/2012 | 3/16/2012 | A | DONE |
Dave Hannah
|
|
|
Jerry @ ###-####
|
GCB-Energy | 3/12/2012 | 3/13/2012 | 3/13/2012 | A | PASS |
Mike Jordan
|
|
|
Jerry @ ###-####. OK to sheet rock.
|
GCB-Framing | 3/12/2012 | 3/12/2012 | 3/12/2012 | P | PASS |
Mike Jordan
|
|
|
Jerry Phone #: ###-####. Airseal and fireblock completed. Ok to insulate.
|
GCB-Framing | 3/8/2012 | 3/9/2012 | 3/9/2012 | A | PART |
Mike Jordan
|
|
|
Jerry @ ###-####. Framing ok. Needs to complte sirseal and fire stop penetrations through top plates and at ceiling level along existing building.
|
GCB-Masonry | 2/21/2012 | 2/22/2012 | 2/22/2012 | A | PART |
Dave Hannah
|
|
|
Jerry @ ###-####Rebar crew is toping out last lift
|
GCB-Masonry | 2/17/2012 | 2/17/2012 | 2/17/2012 | P | PASS |
Tom Arcoraci
|
|
|
|
GCB-Masonry | 2/16/2012 | 2/17/2012 | 2/17/2012 | A | CANC |
Tom Arcoraci
|
|
|
Jerry @ ###-####(Rebar Inspection)
|
GCB-Shearwall | 2/14/2012 | 2/15/2012 | 2/15/2012 | A | PASS |
Mike Jordan
|
|
|
Jerry @ ###-####. Exterior shear nail ok. Reviewed and inspected truss repair from truss enginneer for roof trusses that have benn installed upside down. Inspected the 32/16 span rated osb on both sides with required nailing. ok to cover exterior sheathing only.
|
GCB-Framing | 2/3/2012 | 2/6/2012 | 2/6/2012 | A | FAIL |
Mike Jordan
|
|
|
Jerry @ ###-####. Nails are over driven. Needs to renail. Also need RFI from engineer for repair on roof trusses that have been installed upside down.
|
Routing - PLAN CHECK | 2/2/2012 | | 2/2/2012 | | PASS |
Sam Zahorka
|
|
|
2nd Plan Modification
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/2/2012 | | DONE |
Sam Zahorka
|
|
|
|
CHANGE STATUS TO (ISS) | | | 2/2/2012 | | DONE |
|
|
|
plan modification - changed status back to issue
|
Plan resubmittals received | | | 1/31/2012 | | DONE |
|
|
|
|
CHANGE STATUS TO (REV) | | | 1/31/2012 | | DONE |
|
|
|
plan resubmittals received
|
GCB-Fndatn/slab ins/fld vent | 1/20/2012 | 1/23/2012 | 1/23/2012 | A | PASS |
Dave Hannah
|
|
|
Jerry @ ###-####
|
GCB-Footing | 1/19/2012 | 1/20/2012 | 1/20/2012 | A | PASS |
Dave Hannah
|
|
|
Jerry @ ###-####3 PM Inspection
|
Routing - PLAN CHECK | 12/21/2011 | | 12/28/2011 | | PASS |
Sam Zahorka
|
|
|
Plan modification resubmittals approved.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/28/2011 | | DONE |
Sam Zahorka
|
|
|
|
Issue and Courier | | | 12/28/2011 | | DONE |
|
|
|
plan modification
|
Plan resubmittals received | | | 12/21/2011 | | DONE |
|
|
|
|
CHANGE STATUS TO (REV) | | | 12/21/2011 | | DONE |
|
|
|
|
GCB-Footing | 12/14/2011 | 12/15/2011 | 12/15/2011 | A | PASS |
Mike Jordan
|
|
|
Jerry @ ###-####11 a.m. inspection. Footing ok. Needs to have architect and engineer re-evaluate existing footing and foundation system.
|
Telephone call | | | 12/15/2011 | | DONE |
Sam Zahorka
|
|
|
I spoke with the Structural inspector and Leon and Garden City. The structural inspector Michael Jordan stated the existing wall that the new addition is tying into has no foundation and is sitting on dirt. He has required the Design Professionals to evaluate the existing wall and foundation system.
|
Plan assigned to (SRZ) | 8/10/2011 | 8/10/2011 | 10/12/2011 | | DONE |
Sam Zahorka
|
|
|
|
Routing - PLAN CHECK | 10/12/2011 | | 10/12/2011 | | PASS |
Sam Zahorka
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/12/2011 | | DONE |
Sam Zahorka
|
|
|
|
Issue and Courier | | | 10/12/2011 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 10/11/2011 | | DONE |
Sam Zahorka
|
|
|
Called Jim Escobar and requested Engineering calculations and roof ventilation response information.
|
Plan resubmittals received | | | 10/3/2011 | | DONE |
|
|
|
|
Telephone call | | | 9/23/2011 | | DONE |
Sam Zahorka
|
|
|
Telephone call with the architect Jim Escobar. Answered plan review correction questions.
|
Telephone call | | | 9/13/2011 | | DONE |
Sam Zahorka
|
|
|
Spoke with the architect about corrections. Answered his questions and emailed an alternate code request template for the exterior wall issues.
|
1st review completed | | | 9/12/2011 | | DONE |
Sam Zahorka
|
|
|
Failed IBC Plan Review. Corrections requested.
|
Plan resubmittals requested | | | 9/12/2011 | | DONE |
Sam Zahorka
|
|
|
|
Routing - PLAN CHECK | 8/10/2011 | | 9/12/2011 | | FAIL |
Sam Zahorka
|
|
|
|
Plan resubmittals received | | | 8/26/2011 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/17/2011 | | DONE |
|
|
|
|
Application received | | | 8/9/2011 | | DONE |
|
|
|
|