Permit Information
Permit NumberGCB12-00028
StatusFinaled
Name ALC Architecture
Site Address 6720 N GLENWOOD ST STE 7003
Project NameBLD2012-00029
Customer Number 
ePlanReviewNo
Description
(Ross Dress For Less) - ***5-17-12 PLAN MODIFICATION TO INCLUDE: THE ADDITION OF MECHANICAL ROOF TOP UNITS AND MECHANICAL UPGRADES PER THE UPDATED ENGINEERING AND APPROVED PLANS. SRZ *** To remodel an existing 25,275 square foot Mercantile tenant space per the approved plans. The North West wall is shared with Big Lots. The South East wall is shared with Big 5 Sporting Goods. Work to include: Demolition work per plans; construct new interior walls to create new offices, locker room, equipment & janitorial closets, electrical room, processing room, accessible mens & womens fitting and restrooms, fire riser room, sales floor, and exit corridor; install a new dual height (hi-lo) accessible drinking fountain; install a service sink; related interior finishes in compliance with chapter 8 of the 2009 IBC; new store front glazing and door system at the entrance & vestibule per plans; install new footings, columns, beams, & cmu walls at front entry canopy per plans; install (3) new roof top units; construct new canopy at the receiving door location; new exterior/interior lighting and exterior site upgrades per plans; Mechanical, plumbing, and electrical work; and all other work per the approved plans, attached plan review report, engineering, and applicable adopted codes. NOTE: This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. A new Certificate of Occupancy with the new occupant load total is required to be obtained after all work has been inspected and approved and prior to tenant occupying this space. **SRZ**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
GCB-Final8/14/20128/14/20128/14/2012PPASS
DetailsDave Hannah
Steve @ ###-####
PM Inspection
GCB-Framing7/17/20127/18/20127/18/2012APART
DetailsMike Jordan
Robert @ ###-####
AM inspection requested
Framing for facade. Needs to provide the correct track splice at corners and justify condition of simpson holdowns. ok to cover.
GCB-Shearwall7/11/20127/12/20127/12/2012APASS
DetailsMike Jordan
Robert @ ###-####. Shear walls for new store front ok.
GCB-Ceiling Grid7/9/20127/10/20127/10/2012APASS
DetailsMike Jordan
Robert @ ###-####. Hardlids ok to cover.
GCB-Framing7/6/20127/9/20127/9/2012PCANC
DetailsMike Jordan
Robert @ ###-####
PM Inspection
GCB-Framing7/3/20127/5/20127/5/2012APART
DetailsDave Hannah
Robert @ ###-#### ext front soffiot ok to one side
GCB-Footing6/27/20126/28/20126/28/2012PFAIL
DetailsMike Jordan
Robert @ ###-####
PM Inspection. Footing for compactor pad, Verts exceed the 16" O.C. spacing as shown on RFI and needs to provide 3" of clearance from bottom of footing to bottom of rebar. Correction notice was issued. MTI will verify repairs prior to placement and note on report.
GCB-Energy6/18/20126/19/20126/19/2012APASS
DetailsDave Hannah
Robert @ ###-#### ok to cover ext walls
GCB-Framing6/14/20126/15/20126/15/2012PPASS
DetailsDave Hannah
Robert @ ###-####
PM Inspection ok to cover int walls ok to insulate ext walls
GCB-Footing5/24/20125/24/20125/24/2012PPASS
DetailsTom Arcoraci
pending spec insp by mti
GCB-Footing5/23/20125/24/20125/24/2012ACANC
DetailsTom Arcoraci
ROBERT @ ###-#### changed to pm per rob
GCB-Masonry5/21/20125/22/20125/22/2012APASS
DetailsMike Jordan
Robert @ ###-####
Inspection requested for as close to 9 a.m. as possible. 0 to 4ft. elevation at storefront. Also verified special inspections.
Plan assigned to (SRZ)5/15/20125/15/20125/18/2012 DONE
DetailsSam Zahorka
Routing - PLAN CHECK5/15/2012 5/18/2012 PASS
DetailsSam Zahorka
PLANS/APPL TAKEN TO FRONT DESK  5/18/2012 DONE
DetailsSam Zahorka
Issue and Courier  5/18/2012 DONE
DetailsChristina Prado
GCB-Fndatn/slab ins/fld vent5/15/20125/16/20125/16/2012APART
DetailsDave Hannah
Rob @ ###-####
Call in advance to coordinate. Stemwall for canopy columns. Will have special inspection. Also noted to contractor that special inspection firm needs to be contracted by the owner or desighn professional as per IBC capter 17 sec1703.1.1 and sec1704.1. Will give general contractor until next inspection to have issue resolved.
GCB-Footing5/14/20125/15/20125/15/2012ACANC
DetailsJim Sly
Robert @ ###-#### Late AM inspection requested.Late AM inspection requested.Call in advance
Duplicate added in by mistake.......Approx 34 min for inspection. Jim Sly ###-####
GCB-Footing5/14/20125/15/20125/15/2012APASS
DetailsJim Sly
Robert @ ###-####
Late AM inspection requested.
Call in advance
Al lfootings OK .....Pending MTI special inspection, tests and approvals.
Plan resubmittals received  5/15/2012 DONE
DetailsChristina Prado
Received three sets of plans marked A0.0, A1.1, S2.1, S7.3, M1.0, M2.0, M3.1M4.0, M5.0, E5.0 & E6.0. Plans routed to Sam for further review
Plan assigned to (SRZ)3/19/20123/19/20124/16/2012 DONE
DetailsSam Zahorka
1st Review completed. Waiting for resubmittals.
Plan resubmittals received  4/16/2012  
Routing - PLAN CHECK4/16/2012 4/16/2012 PASS
DetailsSam Zahorka
PLANS/APPL TAKEN TO FRONT DESK  4/16/2012 DONE
DetailsSam Zahorka
Issue and Courier  4/16/2012 DONE
DetailsChristina Prado
Routing - PLAN CHECK3/19/2012 4/11/2012 FAIL
DetailsSam Zahorka
Corrections sent to the architect.
1st review completed  4/11/2012 DONE
DetailsSam Zahorka
Telephone call  4/11/2012 DONE
DetailsSam Zahorka
Spoke with the architect Jeff Likes. Verbally discussed comments and corrections. He verified all fire wall compliance questions including horizontal projections and rated opening questions. All existing Firewalls concerning their continuity are in compliance. The existing glycol sprinkler protection in the front canopy will changed to a new dry system without conditioning of the canopy envelope.
Application received  3/16/2012 DONE