GCE-Final | 1/14/2010 | 1/15/2010 | 1/15/2010 | A | PASS |
Doug A Poedy
|
|
|
Contact Zen @ ###-####. Ok final.
|
GCE-Final | 1/13/2010 | 1/14/2010 | 1/14/2010 | A | NR |
Doug A Poedy
|
|
|
Contact Zen @ ###-####. No access to one of the large rooms. It was sealed off and being painted.
|
GCE-Rough-In | 1/4/2010 | 1/5/2010 | 1/5/2010 | A | PASS |
Jack Frank
|
|
|
Contact Zen @###-#### ceilings ok
|
GCE-Rough-In | 12/30/2009 | 12/31/2009 | 12/31/2009 | A | FAIL |
Bob Reichert
|
|
|
Contact Zen @###-####Please contact Zen prior to come in for inspection.The applicant wants the inspector to look at electrical Ceiling. called, left correction notice, NEC 362.30(A) ent shall be securely fastened within 3' of box and every 3', 330.30(B) mc cable shall be secured within 12" of boxes, 110.12(A) shall close boxes- install cover,725.25 accessible portions of abandoned cl 2,3, pltc cables shall be removed, 300.11(A) cables and raceways shall not be supported by ceiling grids, no esc this project
|
GCE-Rough-In | 12/21/2009 | 12/22/2009 | 12/22/2009 | A | PASS |
Doug A Poedy
|
|
|
Contact Zen @###-####. Ok to cover all walls.
|
GCE-Rough-In | 12/18/2009 | 12/21/2009 | 12/21/2009 | A | PART |
Doug A Poedy
|
|
|
For any questions, contact Zen @###-####. Ok to cover worship room ceiling.
|
GCE-Rough-In | 12/18/2009 | 12/18/2009 | 12/18/2009 | P | NR |
Jack Frank
|
|
|
zen Phone #: ###-#### see am request
|
GCE-Rough-In | 12/17/2009 | 12/18/2009 | 12/18/2009 | A | NR |
Jack Frank
|
|
|
Contact Zen @###-#### still needs fire alarm system dropped to new hard ceiling, too many 4 sq extensions on exit light boxes also free length of conductor met contr on job
|
GCE-Rough-In | 12/15/2009 | 12/17/2009 | 12/17/2009 | A | FAIL |
Doug A Poedy
|
|
|
Contact Zen@###-####. Inspection was for left hand side of building. Ceiling is going to be hard lid and there are many j-boxes that will no longer be accessible. NEC 314.29
|
Application received | | | 12/15/2009 | | DONE |
|
|
|
|