GCE-Rough-In Permanent Service | 1/25/2010 | 1/26/2010 | 1/26/2010 | A | PASS |
Doug A Poedy
|
|
|
Contact # ###-#### P/S O/H Reconnect ok.
|
GCE-Rough-In Permanent Service | 1/19/2010 | 1/20/2010 | 1/20/2010 | A | FAIL |
Bob Reichert
|
|
|
Contact Brian @ ###-####Owner Apryl @###-#### Ext 101 called, left correction notice, NEC 250.52(A)(5) shall use 5/8" ground rods, 250.56 shall augment ground rod, 312.5 shall provide abrasion protection, 3120.16 shall provide overcurrent protection per code, 406.8(B) receptacle shall be weather resistant listed type, 210.8 receptacle shall be gfci type, 250.119 shall identify gec per code
|
Application received | | | 1/19/2010 | | DONE |
|
|
|
|