GCE-Final | 4/30/2010 | 5/3/2010 | 5/3/2010 | A | PASS |
Doug A Poedy
|
|
|
(Mandatory Inspection)Scope of inspection: FinalContact: Skip @ ###-####. All corrections made except ul listing on machine. Machine scheduled to be removed.
|
GCE-Final | 4/28/2010 | 4/29/2010 | 4/29/2010 | A | FAIL |
Bob Reichert
|
|
|
(Mandatory Inspection)Scope of inspection: FinalContact: Tim @ ###-####Customer will need A.M. inspection please called, left correction notice, NEC 250.64(C) gec shall only be spliced by irreversible connectors, 250.92 (B) shall bond service raceways, 210.5 shall identify conductors, 110.12(A) shall close unused openings in equipment, 350.30 shall secure fmc within 12" of termination, BCC 4-05-33(A)&(B) all equipment shall be listed by a nationally recognized testing laboratory, NOTE corrections shall be made within 10 working days or further action will be taken
|
Application received | | | 4/19/2010 | | DONE |
|
|
|
|