GCE-Permanent Service | 11/3/2010 | 11/4/2010 | 11/4/2010 | A | PASS |
Bob Reichert
|
|
|
Scope: Perm ServiceContact: Brent @ ###-#### p/s o/h rec ok
|
GCE-Permanent Service | 11/1/2010 | 11/2/2010 | 11/2/2010 | A | FAIL |
Bob Reichert
|
|
|
Scope: Perm ServiceContact: Brent @ ###-#### called, left correction notice, NEC 110.14 shall not intermix conductors of dis-similar metals, 250.19 shall identify equipment grounding conductor, 300.4(G) shall provide conduit bushing, 300.5 shall bury conductors 24", Note: corrections shall be made within 5 working days inspection done by 445
|
Application received | | | 11/1/2010 | | DONE |
|
|
|
|