Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberGCE10-00132
StatusIssued
Name Lee Electric
Site Address 410 E 43RD ST Unit: 1
Project NameELE2010-00134
Customer Number 
ePlanReviewNo
Description
Project description was not supplied.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
GCE-Permanent Service11/3/201011/4/201011/4/2010APASS
DetailsBob Reichert
Scope: Perm ServiceContact: Brent @ ###-#### p/s o/h rec ok
GCE-Permanent Service11/1/201011/2/201011/2/2010AFAIL
DetailsBob Reichert
Scope: Perm ServiceContact: Brent @ ###-#### called, left correction notice, NEC 110.14 shall not intermix conductors of dis-similar metals, 250.19 shall identify equipment grounding conductor, 300.4(G) shall provide conduit bushing, 300.5 shall bury conductors 24", Note: corrections shall be made within 5 working days inspection done by 445
Application received  11/1/2010 DONE