GCE-Temporary Service | 1/14/2011 | 1/18/2011 | 1/18/2011 | A | PASS |
Bob Reichert
|
|
|
Scope: Temp ServiceContact: Jeremy @ ###-#### n corrections made, t/s u/g n ok
|
GCE-Temporary Service | 1/12/2011 | 1/13/2011 | 1/13/2011 | A | FAIL |
Bob Reichert
|
|
|
Scope: Temp ServiceContact: Jeremy @ ###-#### called, left correction notice, NEC 408.4 shall provide circuit schedule, 312.5 shall provide abrasion protection, 110.14(A) shall tighten terminations, 230.71(B) shall provide suitable handle tie at trailer main, 400.5 shall provide minimum #4 flexible cord for 60A main and trailer service, 400.10 shall provide strain relief for cords at fittings, 400.14 shall protect cable from damage, BCC shall provide job id sticker
|
Application received | | | 1/11/2011 | | DONE |
|
|
|
|