DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
GCE-Final10/10/201210/12/201210/12/2012APASS
DetailsRock A. Hudson
Rusty @ ###-####
AM inspection requested Final ok
GCE-Final10/4/201210/4/201210/4/2012PFAIL
DetailsDoug A Poedy
Rusty @ ###-####. Numerous pre-existing code violations. High leg on a phase, k/o seals in panel, Bryant breaker in GE panel, bond wire to service nipple size 12 and should be 4.
Application received  10/4/2012 DONE