GCE-Final | 5/8/2013 | 5/9/2013 | 5/9/2013 | A | PASS |
Rock A. Hudson
|
|
|
Alan ###-#### Please call in advance
Final ok
|
GCE-Final | 2/25/2013 | 2/26/2013 | 2/26/2013 | A | CANC |
Rock A. Hudson
|
|
|
Alan @ ###-#### Needed rough in insp.
|
GCE-Rough-In | 2/26/2013 | 2/26/2013 | 2/26/2013 | P | PASS |
Rock A. Hudson
|
|
|
Alan @ ###-#### Rough in ok cover
|
GCE-Rough-In | 2/20/2013 | 2/21/2013 | 2/21/2013 | A | FAIL |
Daryl DeGrange
|
|
|
Allen @ ###-#### Not all corrections completed
|
GCE-Rough-In | 2/15/2013 | 2/15/2013 | 2/15/2013 | P | FAIL |
Rock A. Hudson
|
|
|
Allan Phone #: ###-#### 2 requests posted. Editted AM request
|
GCE-Rough-In | 2/15/2013 | 2/15/2013 | 2/15/2013 | A | FAIL |
Rock A. Hudson
|
|
|
Allan ###-#### NEC 300.4(A)(1) Cables need protected where bored holes are less than 1 1/4" from nearest edge of wood member. NEC 300.4(D) Cable shall not be installed or supported less than 1 1/4" from nearest edge of framing member. Phone number provided on inspection request was wrong number. Unable to contact contractor.
|
Application received | | | 2/4/2013 | | DONE |
|
|
|
|