GCE-Final | 9/12/2013 | 9/12/2013 | 9/13/2013 | P | PASS |
Rock A. Hudson
|
|
|
###-#### Final ok
|
GCE-Final | 9/11/2013 | 9/11/2013 | 9/11/2013 | P | FAIL |
Rock A. Hudson
|
|
|
###-#### 352.30 (A)- Service riseer shall be secured with in 3 ft of box. 210.12 (B) Bedroom arc fault breaker will not trip. 314.20 Box or extension ring shall not be set back more than 1/4". Spark ring required
|
GCE-Rough-In Permanent Service | 7/12/2013 | 7/12/2013 | 7/12/2013 | P | PASS |
Daryl DeGrange
|
|
|
Brandon ###-#### rough-in p/s u/g n ok with unattached garage
|
Application received | | | 5/22/2013 | | DONE |
|
|
|
|