GCE-Temporary Service | 7/11/2013 | 7/11/2013 | 7/12/2013 | P | PASS |
Rock A. Hudson
|
|
|
Jim ###-#### Corrections done t/s o/h n ok
|
GCE-Temporary Service | 7/10/2013 | 7/10/2013 | 7/10/2013 | P | FAIL |
Rock A. Hudson
|
|
|
Jim ###-#### 250.24(A)- Grounding electode conductor shall terminate at same bus bar as grounded electode. 590.6(B)(1)- 240 volt receptical shall be GFCI protected
|
Application received | | | 7/10/2013 | | DONE |
|
|
|
|