GCE-Final | 3/14/2014 | 3/17/2014 | 3/17/2014 | P | PASS |
Rex Boyles
|
|
|
Tom ###-#### please call 30 minutes before final ok corrections made
|
GCE-Final | 3/14/2014 | 3/14/2014 | 3/14/2014 | P | FAIL |
Rex Boyles
|
|
|
(Mandatory Inspection) Thomas ###-#### Bond nuetral bar to case of transformer with #4 min. Move 3/0 building ground conductor to case of transformer. Label upside down 250amp main to show on and off positions. (Should always be up in the on position) address on new meter
|
GCE-Rough-In Permanent Service | 2/19/2014 | 2/20/2014 | 2/20/2014 | P | PART |
Rock A. Hudson
|
|
|
Thomas ###-#### 250.30 (A)(6) Structural steel shall be connected to the grounded conductor of the separatly derived system. 250.97 for circuits over 250 volt to ground, metal raceways shall be bonded (metal raceway to transformers.) (primary side) u/g ok to cover. p/s u/g n ok
|
Application received | | | 2/6/2014 | | DONE |
|
|
|
|