GCE-Final | 10/15/2014 | 10/16/2014 | 10/16/2014 | P | PASS |
Rock A. Hudson
|
|
|
(Mandatory Inspection) Signed card Final ok
|
GCE-Final | 9/30/2014 | 10/1/2014 | 10/1/2014 | A | PASS |
Rex Boyles
|
|
|
Steve ###-#### final ok
|
GCE-Permanent Service | 8/19/2014 | 8/22/2014 | 8/22/2014 | A | PASS |
Rex Boyles
|
|
|
Steve ###-#### or office ###-#### please call half hour advance r/i p/s n ok (new switchgear)
|
GCE-Rough-In | 7/30/2014 | 7/31/2014 | 7/31/2014 | A | PASS |
Rex Boyles
|
|
|
Steve ###-#### - re-inspect corrections made r/i ok
|
GCE-Rough-In | 7/29/2014 | 7/30/2014 | 7/30/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Steve ###-#### 300.4- MC when ran through bored holes that do not maintain 1 1/4" from framing surface protection from physical damage shall be installed. 300.11- Luminaires and outlet boxes shall have indepenant support form ceiling support system. 300.11- Luminaires and outlet boxes shall be independantly supported from ceiling support system.
|
GCE-Courtesy | 3/20/2014 | 3/21/2014 | 3/20/2014 | A | DONE |
Rock A. Hudson
|
|
|
Doug Phone #: ###-#### Discussed using bottom of I-line type panelboard as raceway to access conduits originally installed in concrete below panelboard. 312.8- States as long as adequate space is available for additional wires it can be used.
|
Application received | | | 3/19/2014 | | DONE |
|
|
|
|