GCE-Final | 5/15/2014 | 5/15/2014 | 5/15/2014 | P | PASS |
Rex Boyles
|
|
|
aaron ###-#### final on shop bldg. ok
|
GCE-Final | 4/29/2014 | 4/30/2014 | 4/30/2014 | A | NR |
Rock A. Hudson
|
|
|
Aaron ###-#### Kahala Electric Added a bathroom which is at rough in stage
|
GCE-Rough-In | 4/30/2014 | 4/30/2014 | 4/30/2014 | P | PASS |
Rock A. Hudson
|
|
|
Aaron ###-#### Kahala Electric Bathroom rough in ok cover
|
GCE-Rough-In | 3/31/2014 | 3/31/2014 | 3/31/2014 | P | DONE |
Rex Boyles
|
|
|
AARON ###-#### needed perm. service
|
GCE-Permanent Service | 3/31/2014 | 3/31/2014 | 3/31/2014 | P | PASS |
Rex Boyles
|
|
|
AARON ###-#### p/s o/h n ok maintain min. 3foot above residence roof!
|
GCE-Rough-In | 3/28/2014 | 3/31/2014 | 3/31/2014 | A | FAIL |
Rex Boyles
|
|
|
aaron ###-#### 250.52(A)(2)- bond service to building steel. 250.53(A)- grounding electrode system consisting of 2- ground rods required. 250.32(D) (2)-separate grounding electrode required for separate building consisting of more than one circuit.
|
Application received | | | 3/28/2014 | | DONE |
|
|
|
|