GCE-Rough-In Permanent Service | 5/20/2014 | 5/20/2014 | 5/21/2014 | P | PASS |
Rex Boyles
|
|
|
Joel Smith ###-#### call for access; installer will meet inspector rough in ok p/s u/g n ok (existing meter pack)
|
GCE-Final | 5/21/2014 | 5/21/2014 | 5/21/2014 | P | PASS |
Rex Boyles
|
|
|
Joel Smith ###-#### call for access; installer will meet inspector final ok
|
GCE-Permanent Service | 5/19/2014 | 5/20/2014 | 5/20/2014 | A | FAIL |
Bob Reichert
|
|
|
Steve ###-#### inspection requested for as early as possible called, left correction notice, left card, NEC 230.2(E) shall provide permanent plaque at service disconnect, 110.22 shall identify disconnect, 110.12(A) shall close unused openings, BCC 4-05-24(D) shall provide access, fee due
|
GCE-Inspection Hourly Charge | 5/20/2014 | 5/20/2014 | 5/20/2014 | P | PASS |
Bob Reichert
|
|
|
Steve ###-#### inspection requested for as early as possible 1 hour re-inspection fee
|
Application received | | | 5/19/2014 | | DONE |
|
|
|
|