GCE-Final | 9/11/2014 | 9/11/2014 | 9/11/2014 | P | PASS |
Rex Boyles
|
|
|
Rich ###-#### corrections made final ok
|
GCE-Final | 9/9/2014 | 9/9/2014 | 9/9/2014 | P | FAIL |
Daryl DeGrange
|
|
|
Rich ###-#### Receptacle under kitchen peninsula has been removed leaving wiring exposed.
|
GCE-Rough-In Permanent Service | 7/1/2014 | 7/1/2014 | 7/1/2014 | P | PASS |
Rock A. Hudson
|
|
|
(Mandatory Inspection) Rich ###-#### Rough in ok cover p/s u/g n ok
|
GCE-Rough-In Permanent Service | 6/30/2014 | 6/30/2014 | 6/30/2014 | P | FAIL |
Rock A. Hudson
|
|
|
All Phaase Electric ###-#### 300.4 NM cable when ran thru stud shall maintain 1 1/4" from framing surface, if not shall be protected from physical damage with nail plate. Wire to out garage lights and pantry light.
|
Application received | | | 6/27/2014 | | DONE |
|
|
|
|