GCE-Final | 10/24/2014 | 10/24/2014 | 10/24/2014 | P | PASS |
Rex Boyles
|
|
|
Daniel ###-#### corrections made final ok
|
GCE-Final | 10/23/2014 | 10/23/2014 | 10/23/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Daniel ###-#### Corrections not all addreseed, 406.8 Outside receptacles to be of a weather resistant type
|
GCE-Final | 10/22/2014 | 10/23/2014 | 10/23/2014 | A | FAIL |
Rex Boyles
|
|
|
(Mandatory Inspection) call for access code 210.8(A)(3)- GFCI protection required on exterior receptacles. Missing receptacle cover in kitchen and living room cabinet.
|
GCE-Permanent Service | 8/13/2014 | 8/13/2014 | 8/13/2014 | P | DONE |
Daryl DeGrange
|
|
|
Daniel ###-#### correction done, p/s u/g n ok
|
GCE-Permanent Service | 8/12/2014 | 8/12/2014 | 8/12/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Daniel ###-#### 250.4(A)(1)- Grounded electrical systems shall be connected to earth in an approved manner. Ground electorde systym shall be provided and connected to service.
|
GCE-Rough-In Permanent Service | 8/4/2014 | 8/4/2014 | 8/4/2014 | P | FAIL |
Rex Boyles
|
|
|
Daniel ###-#### need to install ground rods grounding electrode rebar is exposed in dirt outside bldg. and not usable
|
GCE-Rough-In | 8/4/2014 | 8/4/2014 | 8/4/2014 | P | PASS |
Rex Boyles
|
|
|
Daniel ###-#### r/i ok
|
Application received | | | 7/31/2014 | | DONE |
|
|
|
|