GCE-Final | 3/10/2015 | 3/11/2015 | 3/11/2015 | A | PASS |
Rex Boyles
|
|
|
Daniel ###-#### corrections made final ok
|
GCE-Final | 3/10/2015 | 3/10/2015 | 3/10/2015 | P | FAIL |
Rex Boyles
|
|
|
guest room GFI not resetting, loose receptacles interior and exterior, elevator disconnect door won't open for access.
|
GCE-Rough-In | 12/12/2014 | 12/15/2014 | 12/15/2014 | A | PASS |
Rex Boyles
|
|
|
Ultimate Electric ###-#### r/i for conduit and wiring to solar invertor ok
|
GCE-Rough-In Permanent Service | 10/29/2014 | 10/29/2014 | 10/30/2014 | P | PASS |
Rex Boyles
|
|
|
Daniel ###-#### r/i ok p/s u/g n ok secondary conduit not deep enough!?
|
GCE-Rough-In Permanent Service | 10/21/2014 | 10/21/2014 | 10/21/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Daniel ###-#### 210.52(A)(2) Pocket door, and stair rail wall space shall have receptacle outlets, reading nook under stairs 300.4 NM and Low Volt cable through bored holes that do not maintain 1 1/4 inches from framing surface shall be protected from physical damage 300.4 B 1 Fireplace, nm cable shall enter through bushed hole 334.30 NM Cable shall be supported at integrals not exceeding 4.5 feet 334.30 do not stack staples, can damage cable low volt wiring under truss
|
Application received | | | 9/30/2014 | | DONE |
|
|
|
via Garden City Web Service
|