GCE-Final | 11/6/2014 | 11/6/2014 | 11/6/2014 | P | PASS |
Rex Boyles
|
|
|
Cal ###-#### corrections made final ok
|
GCE-Final | 11/5/2014 | 11/5/2014 | 11/5/2014 | P | FAIL |
Rex Boyles
|
|
|
Cal ###-#### update panel schedules, 210.8(B)(7)-GFCI protection required within 6 foot of sink. 210.62-show windows need receptacle every 12 foot. 220.14-show windows require 200 va per foot
|
GCE-Rough-In | 10/6/2014 | 10/6/2014 | 10/6/2014 | P | PASS |
Rex Boyles
|
|
|
Cal ###-#### building should be open corrections made r/i ok p/s u/g n ok
|
GCE-Rough-In | 10/3/2014 | 10/3/2014 | 10/6/2014 | P | CANC |
Rex Boyles
|
|
|
Cal ###-#### called in late friday and never inspected. Cal called in again for 10/6/14
|
Application received | | | 10/3/2014 | | DONE |
|
|
|
via Garden City Web Service
|