GCE-Final | 12/17/2014 | 12/18/2014 | 12/18/2014 | A | PASS |
Cevyn Recla
|
|
|
Jeff ###-#### Final OK
|
GCE-Rough-In | 10/29/2014 | 10/29/2014 | 10/29/2014 | P | PASS |
Rex Boyles
|
|
|
Jeff ###-#### corrections made r/i ok
|
GCE-Permanent Service | 10/28/2014 | 10/29/2014 | 10/29/2014 | A | PASS |
Rex Boyles
|
|
|
Jeff ###-#### p/s u/g n ok
|
GCE-Rough-In | 10/28/2014 | 10/29/2014 | 10/29/2014 | A | FAIL |
Rex Boyles
|
|
|
Jeff ###-#### no corrections made re inspection fee as per Garden city
|
GCE-Rough-In | 10/27/2014 | 10/28/2014 | 10/28/2014 | P | FAIL |
Rex Boyles
|
|
|
Jeff ###-#### 300.4 (D)-11/4 inches required from edge of stud to nm cable. 334.30-nm cable shall not be stapled on the edge. 320.23(A)- gaurd strip required for nm cable within 6 foot of attic access. Finish exterior boxes and nm cable installation. Remove plastic of top of recessed cans.
|
Application received | | | 10/27/2014 | | DONE |
|
|
|
via Garden City Web Service
|