GCE-Final | 2/12/2015 | 2/12/2015 | 2/13/2015 | P | PASS |
Cevyn Recla
|
|
|
Heather ###-#### COrrections made, Final OK
|
GCE-Final | 2/10/2015 | 2/10/2015 | 2/10/2015 | P | FAIL |
Cevyn Recla
|
|
|
Heather ###-#### 408.36 (D) Back-Fed Devices. Plug-in-type overcurrent protection devices or plug-in type main lug assemblies that are backfed and used to terminate field-installed ungrounded supply conductors shall be secured in place by an additional fastener that requires other than a pull to release the device from the mounting means on the panel. 422.31 Disconnecting means required for permanently installed appliances 422.31 Disconnecting means shall be provided for all permanently installed appliances 330.30 MC shall be secured within 12 inches of connector 356.30 LFNC shall be secured within 12 inches of connector 406.9 all 15 and 20 amp receptacles in damp or wet location shall be weather resistant type 408.4 Every circuit shall be legibly identified 422.31 Overcurrent rating shall not exceed the device rating marked on the appliance
|
GCE-Rough-In | 12/15/2014 | 12/16/2014 | 12/16/2014 | A | PASS |
Rex Boyles
|
|
|
###-#### r/i ok new walls and ceilings
|
Application received | | | 11/24/2014 | | DONE |
|
|
|