GCE-Final | 2/3/2015 | 2/3/2015 | 2/3/2015 | P | PASS |
Rex Boyles
|
|
|
###-#### corrections made final ok
|
GCE-Final | 1/27/2015 | 1/28/2015 | 1/28/2015 | A | FAIL |
Rex Boyles
|
|
|
Penny ###-#### 406.5(C)-receptacles mounted to covers shall have more than on screw, 210.4(B)-where a multiwire branch circuit feeds one device both circuits shall be disconnected simultaneuosly. 348.30-flexable metal conduit shall be secured within 12inches of cabinet. (Also locknut is loose). 358.30-EMT shall be secured within 3 foot of cabinet. 300.4(G)-#4 conductors and larger shall be protected by an insulated fitting or plastic bushing. 408.7-unused openings shall be closedwith KO seals.
|