GCE-Final | 6/30/2015 | 7/1/2015 | 7/1/2015 | A | PASS |
Rex Boyles
|
|
|
Ben ###-#### final ok o/s fixtures listed
|
GCE-Final | 6/24/2015 | 6/25/2015 | 6/25/2015 | A | PART |
Rex Boyles
|
|
|
Ben ###-#### corrections made. Temp. occupancy OK. Also r/i ok on 2 pole bases. waiting on light poles to show up to get final.
|
GCE-Final | 6/23/2015 | 6/24/2015 | 6/24/2015 | A | FAIL |
Rex Boyles
|
|
|
Ben ###-#### 110.24(A)- fault current needs date also. Exterior light pole or sign bases not poured and no wire installed in raceways??
|
GCE-Final | 6/22/2015 | 6/22/2015 | 6/22/2015 | P | FAIL |
Rex Boyles
|
|
|
Ben ###-#### 110.16-all commercial panels shall have arc flash warning label. 110.24(B)- service equiptment in other than dwelling units shall be permanently marked in the field with the maximum available fault current. 314.20- boxes shall be installed so that the front edge of the box is not more than 1/4 inch. In walls and ceilings constructed of wood or other combustable surface material (FRP adhesive) , box extensions shall be used.
|
GCE-Rough-In Permanent Service | 5/19/2015 | 5/20/2015 | 5/20/2015 | A | PASS |
Rex Boyles
|
|
|
Ben ###-#### r/i ok p/s u/g n ok
|
GCE-Rough-In | 4/27/2015 | 4/28/2015 | 4/28/2015 | A | PASS |
Rex Boyles
|
|
|
Ben ###-#### r/i exterior u.ground ok to cover
|
Application received | | | 4/27/2015 | | DONE |
|
|
|
via Garden City Web Service
|