GCE-Final | 7/23/2015 | 7/24/2015 | 7/24/2015 | A | PASS |
Rex Boyles
|
|
|
Calvin ###-#### corrections made final ok
|
GCE-Final | 7/17/2015 | 7/20/2015 | 7/20/2015 | A | FAIL |
Bob Reichert
|
|
|
Clay ###-#### - key under rock at north side door called, left correction notice, NEC 408.4 panel schedule shall be clear, concise, evident, 408.7 shall close unused openings in panel, 300.11 cables and raceways shall not be supported by ceiling grids, 725.25 shall remove abandoned lv cables
|
GCE-Rough-In | 7/6/2015 | 7/6/2015 | 7/6/2015 | P | PASS |
Rex Boyles
|
|
|
Ceiling grid ###-#### r/i ceilings ok except hall where data is getting relocated
|
GCE-Rough-In | 6/3/2015 | 6/4/2015 | 6/4/2015 | A | PASS |
Eric Story
|
|
|
Calvin ###-#### rouh-in walls ok cover
|
GCE-Rough-In | 6/1/2015 | 6/2/2015 | 6/2/2015 | A | FAIL |
Daryl DeGrange
|
|
|
Calvin ###-#### NEC 330.12(1) Installed where subject to physical damage (inside 2x4 framing member), 1 1/4, Stall secure EMT raceway within 3 ft of box
|
GCE-Rough-In | 5/29/2015 | 6/1/2015 | 6/1/2015 | A | NR |
Rex Boyles
|
|
|
Calvin ###-#### still no approved plans on site
|
GCE-Rough-In | 5/28/2015 | 5/29/2015 | 5/29/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Calvin ###-#### no approed print on site unavailable to verify buiding identification
|
Application received | | | 4/29/2015 | | DONE |
|
|
|
via Garden City Web Service
|