GCE-Final | 6/23/2016 | 6/24/2016 | 6/24/2016 | A | PASS |
James Ady
|
|
|
Brandon ###-#### - code: 5056 Correction made. Final ok
|
GCE-Final | 6/21/2016 | 6/21/2016 | 6/21/2016 | P | FAIL |
James Ady
|
|
|
Brandon ###-#### 210.8 A 3. Outdoor recepticles shall be GFCI Protected. ( Back patio recep Not protected and Hot Nuetral reversed)
|
GCE-Rough-In Permanent Service | 12/9/2015 | 12/8/2015 | 12/10/2015 | P | PASS |
Rex Boyles
|
|
|
Brandon ###-#### corrections made r/i ok p/s u/g n ok
|
GCE-Rough-In Permanent Service | 12/4/2015 | 12/7/2015 | 12/7/2015 | P | FAIL |
Rex Boyles
|
|
|
Brandon ###-#### 310.15(B)(7)- #2 alum only good for 75amps. OK to install 80 amp breaker as per 240.4(B) 300.4(A)(1)- nailplates need upst. bdrms, kitchen, upst. bath. 334.30-support and secure ser at sub panel and main service. load calcs recommended for sub panel
|
Application received | | | 12/4/2015 | | DONE |
|
|
|
via Garden City Web Service
|