GCE-Final | 1/28/2016 | 1/29/2016 | 1/29/2016 | A | PASS |
Rex Boyles
|
|
|
Greg ###-#### corrections made final ok
|
GCE-Final | 1/27/2016 | 1/28/2016 | 1/28/2016 | A | FAIL |
Rex Boyles
|
|
|
Greg ###-#### corrections not made
|
GCE-Final | 1/26/2016 | 1/27/2016 | 1/27/2016 | A | FAIL |
Rex Boyles
|
|
|
Greg ###-#### - garage code: 3255 Reverse polarity to dining rm receptacle, no cover 2gang box kitchen counter, identify o/s receptacle circuit
|
GCE-Rough-In Permanent Service | 12/13/2015 | 12/10/2015 | 12/14/2015 | A | DONE |
Rex Boyles
|
|
|
Greg ###-#### already inspected ??
|
GCE-Rough-In Permanent Service | 12/9/2015 | 12/10/2015 | 12/10/2015 | A | PASS |
Rock A. Hudson
|
|
|
Greg ###-#### Rough in ok cover p/s u/g n ok
|
GCE-Rough-In | 12/9/2015 | 12/9/2015 | 12/9/2015 | P | FAIL |
Rex Boyles
|
|
|
Greg ###-#### 210.52(G)(1)- the branch circuit supplying garage receptacles shall not supply outlets outside of the garage. metal boxes shall be grounded at rough in stage 320.23(A)- cables run within 6 foot of attic crawl shall be protected with gaurd strips. remove all drywall covering full length of nm cable not yet inspected
|
Application received | | | 12/4/2015 | | DONE |
|
|
|
via Garden City Web Service
|