GCM-Final | 5/19/2011 | 5/23/2011 | 5/23/2011 | A | PART |
Bill VanDegrift
|
|
|
FinalBob @ ###-####Call in advance - AM Inspection temp occ ok needs air balance report should be ready monday
|
GCM-Final | 5/19/2011 | 5/20/2011 | 5/20/2011 | A | NR |
Dixie Fellows
|
|
|
FinalBob @ ###-####Call in advance - AM Inspection...need air balance before you call for a final
|
GCM-Rough-in | 5/2/2011 | 5/3/2011 | 5/3/2011 | A | PART |
Dixie Fellows
|
|
|
Bob-Please call prior to inspection Phone #: ###-####...grease duct welds ok...light test ok
|
GCM-Pressure Test | 4/25/2011 | 4/26/2011 | 4/26/2011 | A | PASS |
Dixie Fellows
|
|
|
Conrad-Call in advance Phone #: ###-####...60lb test from meter to regulator above the hood ok...20lb test from reg to equipment outlets ok
|
GCM-Pressure Test | 4/21/2011 | 4/22/2011 | 4/22/2011 | A | FAIL |
Dixie Fellows
|
|
|
Conrad-Please call in advance Phone #: ###-####...low pressure guage is bad...leak on 60 lb test...called conrad
|
GCM-Pressure Test | 4/20/2011 | 4/21/2011 | 4/21/2011 | A | FAIL |
Dixie Fellows
|
|
|
Conrad-PLease call prior to inspection Phone #: ###-####...need to test line from meter to regulator above grid on 60lb test
|
Routing - Mechanical Review | 4/18/2011 | | 4/18/2011 | | PASS |
Troy James
|
|
|
received plan modification
resubmitted changes too listed type 1 hoods
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/18/2011 | | |
Patricia Smith
|
|
|
|
CHANGE STATUS TO (ISS) | | | 4/18/2011 | | DONE |
|
|
|
|
Issue permit | | | 4/12/2011 | | DONE |
|
|
|
|
Routing - Mechanical Review | 4/7/2011 | | 4/12/2011 | | PASS |
Troy James
|
|
|
|
Telephone call | | | 4/7/2011 | | DONE |
|
|
|
talked to bill and corey on phone and went over corrections needed for resubmittal
|
Routing - Mechanical Review | 4/5/2011 | | 4/6/2011 | | FAIL |
Troy James
|
|
|
emailed corrections to Bill Matter
|
Application received | | 4/5/2011 | | | |
|
|
|
|