Permit Information
Permit NumberGCP10-00078
StatusFinaled
Name PC Plumbing
Site Address 10482 W CARLTON BAY DR Unit: 7
Project NamePLM2010-00080
Customer Number 
ePlanReview 
Description
Project description was not supplied.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
GCP-Final11/4/201011/5/201011/5/2010APASS
DetailsDaryl Spivey
Scope: FinalContact: Raul @ ###-####
GCP-Final11/3/201011/3/201011/3/2010PFAIL
DetailsDaryl Spivey
Same inspection but forgot to assign time............ds
GCP-Final11/2/201011/3/201011/3/2010AFAIL
DetailsDaryl Spivey
Scope: FinalContact: Raul @ ###-####
need to install 2 in. dcva in horizontal, not approved for vertical, need check installed on cold side of recirc tie in, need union on hot side of W/H, and lavs need to have approved tempering device installed..............ds
GCP- Rough-in8/17/20108/18/20108/18/2010APASS
DetailsDaryl Spivey
Scope: Rough-InContact: Raul @ ###-####
needs nail plates installed ..........ds
GCP-Under Floor7/1/20107/2/20107/2/2010APART
DetailsDaryl Spivey
Scope of Inspection: Underfloor (Groundwork)Contact: Raul @ ###-####
waste and vent tested ok............ds
Application received  7/2/2010 DONE