Permit Information
Permit NumberGCP13-00194
StatusFinaled
Name INSELMAN PLUMBING CO
Site Address 9995 W STATE
Project NamePLM2013-00193
Customer Number 
ePlanReviewNo
Description
Grace At State Street - Scope of work includes construction of a 70,679 sq. ft., single story, fully sprinklered, Type VA construction
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
GCP-Final9/16/20149/17/20149/17/2014APASS
DetailsDaryl Spivey
Patty ###-####
GCP-Final9/12/20149/15/20149/15/2014PPART
DetailsBill VanDegrift
###-#### partial final temp occ pk
GCP-Final9/11/20149/12/20149/12/2014PPART
DetailsDaryl Spivey
Inseslman ###-####
kitchen walk thru..........not ready yet.........sinks need to be anchored........ds
GCP-Final9/8/20149/9/20149/9/2014APART
DetailsDaryl Spivey
###-#### Partial final only
all rooms except for 6 are complete.........public restrooms, finish rooms left and kitchen are left to finish.......ds
GCP- Rough-in7/15/20147/16/20147/16/2014APASS
DetailsBill VanDegrift
Wes ###-#### ri ok
GCP- Rough-in7/15/20147/15/20147/16/2014PPASS
DetailsBill VanDegrift
Wes ###-#### ri ok
GCP- Rough-in7/2/20147/3/20147/3/2014APART
DetailsDaryl Spivey
kitchen area
GCP- Rough-in6/24/20146/25/20146/25/2014APART
DetailsJim Johnson
Inselman ###-#### test on D W V and one roof and overflow drain marked on plan,s test ok
GCP- Rough-in6/20/20146/23/20146/23/2014APART
DetailsDaryl Spivey
patty ###-####
as marked on plan........ds
GCP- Rough-in6/19/20146/20/20146/20/2014APART
DetailsDaryl Spivey
Patty ###-####
as marked on plan............ds
GCP- Rough-in6/11/20146/12/20146/12/2014APART
DetailsDaryl Spivey
Inselman ###-####
W/V tested ok as marked.........ds
GCP- Rough-in6/10/20146/11/20146/11/2014APART
DetailsDaryl Spivey
Inselman ###-####
waste and vent tested ok as marked on plan................ds
GCP- Rough-in6/4/20146/5/20146/5/2014APART
DetailsDaryl Spivey
###-####
water tested in area marked on plan.......ds
GCP- Rough-in5/28/20145/29/20145/29/2014APART
DetailsJim Johnson
###-#### D W V and water marked on plan test ok
GCP- Rough-in5/14/20145/15/20145/15/2014APART
DetailsDaryl Spivey
Inselman ###-####
waste and vent tested ok as marked on plans............ds
GCP- Rough-in5/13/20145/14/20145/14/2014APART
DetailsDaryl Spivey
###-####
waste and vent tested ok as marked on plan........ds
GCP- Rough-in5/12/20145/13/20145/13/2014APART
DetailsDaryl Spivey
###-####
waste and vent as marked on plan.........ds
GCP- Rough-in5/9/20145/12/20145/12/2014APART
DetailsDaryl Spivey
###-####
waste and vent tested ok as marked on plan...........ds
GCP- Rough-in5/8/20145/9/20145/9/2014APART
DetailsDaryl Spivey
###-####
waste and vent in areas marked on plan........ds
GCP- Rough-in5/8/20145/8/20145/8/2014PPART
DetailsDaryl Spivey
467.4416
waste and vent tested ok as marked on prints........ds
GCP- Rough-in5/6/20145/7/20145/7/2014PPART
DetailsDaryl Spivey
Inselman Plumbing ###-####
as marked on plans waste and vent only....ds
GCP- Rough-in5/5/20145/6/20145/6/2014APART
DetailsBill VanDegrift
Inselman Plumbing ###-#### dwv 133 through 139 test ok
GCP- Rough-in5/2/20145/5/20145/5/2014APART
DetailsDaryl Spivey
Patty ###-####
as marked on plan tested ok.......ds
GCP- Rough-in4/30/20145/1/20145/1/2014APART
DetailsDaryl Spivey
Patty 467.4416
west side of east end hallway tested ok.......ds
GCP- Rough-in4/29/20144/30/20144/30/2014APART
DetailsDaryl Spivey
Patty ###-#### Grace Assisited Living
east side of east wing wasdte vent and water tested ok............ds
GCP-Under Floor3/28/20143/31/20143/31/2014PPASS
DetailsDaryl Spivey
patty ###-#### groundwork
G/W complete............kitchen area tested ok................ds
GCP-Under Floor3/25/20143/26/20143/26/2014PPART
DetailsDaryl Spivey
Patty ###-#### groundwork inspection
all rooms groundwork done.......kitchen area is left to do............ds
GCP-Under Floor3/18/20143/19/20143/19/2014PPART
DetailsDaryl Spivey
Patty ###-####ground work mid west side ok...........ds
GCP- Rough-in3/17/20143/18/20143/18/2014PPART
DetailsDaryl Spivey
Patty ###-#### groundwork inspection
northwest end tested ok.........ds
GCP-Under Floor3/14/20143/17/20143/17/2014PPART
DetailsDaryl Spivey
Patty ###-####
s/w trunk line and south end plumbing tested.........ds
GCP-Under Floor3/13/20143/14/20143/14/2014PPART
DetailsDaryl Spivey
Patty ###-#### groundwork
G/W done in middle section...........ds
GCP-Under Floor3/10/20143/11/20143/11/2014PPART
DetailsDaryl Spivey
Patty ###-#### groundwork
S/W trunk lines tested ok.....ds
GCP-Under Floor3/10/20143/10/20143/10/2014PNR
DetailsDaryl Spivey
Wes
got rained out...........ds
GCP- Rough-in3/7/20143/10/20143/10/2014ANR
DetailsDaryl Spivey
Patty ###-####
GCP- Rough-in3/6/20143/7/20143/7/2014APART
DetailsBill VanDegrift
Grnkwork, Patty ###-#### small section entering south west corner ok
GCP-Under Floor3/6/20143/6/20143/6/2014PPART
DetailsDaryl Spivey
wes
west-sw area tested ok.........ds
GCP- Rough-in3/4/20143/5/20143/5/2014APART
DetailsDaryl Spivey
###-#### Inselman Plumbing
n/w section...mech rm and salon gw tested ok.........ds
GCP- Rough-in2/28/20143/3/20143/3/2014PPART
DetailsDaryl Spivey
Patty ###-####
g/w on north west end tested ok.......ds
GCP- Rough-in2/19/20142/20/20142/20/2014PPART
DetailsDaryl Spivey
###-####
ground work on 2nd line from east all tested ok...............ds
GCP- Rough-in2/18/20142/19/20142/19/2014PPART
DetailsDaryl Spivey
Patty ###-####
partial G/W tested ok.............ds
GCP- Rough-in2/18/20142/18/20142/18/2014PPART
DetailsDaryl Spivey
###-####
south east g/w tested ok.........ds
GCP- Rough-in2/13/20142/14/20142/14/2014PCANC
DetailsDaryl Spivey
###-#### Inspection cancelled from web by: Barbara Stitt
GCP-Site system2/4/20142/5/20142/5/2014PPART
DetailsDaryl Spivey
Patty Inselman plumbing ###-#### groundwork inspection request
2nd gridline from east...north end groundwork tested ok...........ds
GCP-Site system1/31/20142/3/20142/3/2014APART
DetailsDaryl Spivey
Lane ###-####
partial on south end of second gridline from east side...........tested ok.........ds
GCP-Site system1/30/20141/31/20141/31/2014APART
DetailsDaryl Spivey
###-####
ground work for 2 showers and 2 w/c on north east tested ok...2nd trunk line from east tied in outside bld ok.............ds
GCP- Rough-in1/28/20141/29/20141/29/2014APART
DetailsDaryl Spivey
###-####
grease line into and out of tank and tie in to sanitary tested from just inside bld ok............ds
GCP- Rough-in1/22/20141/23/20141/23/2014APART
DetailsDaryl Spivey
###-####
east end G/W tested ok.........ds
GCP-Under Floor1/21/20141/22/20141/22/2014APART
DetailsDaryl Spivey
###-####
east side g/w testedto column j.........ds
GCP-Under Floor1/17/20141/21/20141/21/2014APART
DetailsDaryl Spivey
Patty ###-#### groundwork inspection
northeast corner tested ok........ds
GCP-Site system1/16/20141/17/20141/17/2014PPART
DetailsDaryl Spivey
###-####
se corner tested ok......ds
GCP-Site system11/26/201311/27/201311/27/2013APART
DetailsDaryl Spivey
Patty ###-####
outside line that ties 2 west side trunk lines together tested ok..........ds
GCP- Rough-in11/21/201311/22/201311/22/2013ACANC
DetailsDaryl Spivey
Patty ###-#### groundwork
GCP-Under Floor11/22/201311/22/201311/22/2013APART
DetailsDaryl Spivey
Patty ###-#### groundwork
north outside lateral connecting 2 east side main drains............tested ok..........ds
GCP- Rough-in11/18/201311/19/201311/19/2013ACANC
DetailsDaryl Spivey
Lane ###-####
GCP-Under Floor11/19/201311/19/201311/19/2013APART
DetailsDaryl Spivey
Lane ###-####
4th trunkline sewer main from east side tested ok...........ds
GCP- Rough-in11/15/201311/18/201311/18/2013ACANC
DetailsDaryl Spivey
Patty ###-####
GCP-Under Floor11/18/201311/18/201311/18/2013APART
DetailsDaryl Spivey
Patty ###-####
3rd main in from east side tested ok........ds
GCP- Rough-in11/14/201311/15/201311/15/2013ACANC
DetailsDaryl Spivey
Patty ###-####
GCP-Under Floor11/15/201311/15/201311/15/2013APART
DetailsDaryl Spivey
Patty ###-####
main trunk line for waste 2nd line from east tested ok.......ds
GCP- Rough-in11/13/201311/14/201311/14/2013APART
DetailsDaryl Spivey
Patty ###-####
partial underground......east end main building drain tested ok..............ds
Application received  11/12/2013 DONE